Bryant 558F User Manual

Page 35

Advertising
background image

AIR DELIVERY — 558D036-150 HORIZONTAL DISCHARGE UNITS (cont)

558D048 (4 TON)

Airflow

(Cfm)

Standard Direct-Drive Motor

Low Speed

High Speed

208 v

230, 460, 575 v

208 v

230, 460, 575 v

ESP

Bhp

Watts

ESP

Bhp

Watts

ESP

Bhp

Watts

ESP

Bhp

Watts

1200

0.93

0.41

458

0.97

0.45

506

1.04

0.51

572

1.09

0.56

632

1300

0.86

0.42

471

0.90

0.46

521

0.96

0.52

589

1.02

0.58

651

1400

0.78

0.45

503

0.84

0.49

556

0.90

0.54

616

0.96

0.60

681

1500

0.73

0.47

536

0.76

0.52

593

0.83

0.56

631

0.89

0.62

698

1600

0.67

0.49

557

0.70

0.54

616

0.75

0.58

654

0.82

0.64

723

1700

0.60

0.52

584

0.63

0.57

646

0.67

0.60

678

0.74

0.66

750

1800

0.51

0.54

610

0.54

0.60

674

0.62

0.62

698

0.69

0.68

772

1900

0.40

0.56

629

0.45

0.62

696

0.54

0.64

720

0.62

0.70

796

2000

0.32

0.58

661

0.33

0.65

731

0.47

0.66

744

0.54

0.73

823

LEGEND

Bhp

Brake Horsepower Input to Fan

ESP

External Static Pressure (in. wg)

FIOP

Factory-Installed Option

Watts — Input Watts to Motor

NOTES:
1. Values include losses for filters, unit casing, and wet coils. See

page 47 for accessory/FIOP static pressure information.

2. Extensive motor and electrical testing on these units ensures that the

full range of the motor can be utilized with confidence. Using

your fan motors up to the wattage ratings shown will not result in nui-
sance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.

3. Use of a field-supplied motor may affect wire sizing. Contact your lo-

cal representative for details.

4. Minimum allowable cfm is 300 cfm/ton.

558D048 (4 TON)

Airflow

(Cfm)

Alternate Direct-Drive Motor

External Static Pressure (in. wg)

0.1

0.2

0.3

0.4

0.6

0.7

0.8

Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts

1200

514

0.15

158

590

0.20

210

657

0.25

263

723

0.30

315

828 0.42

441

876 0.49

510

924 0.55

578

1300

545

0.18

189

615

0.23

242

680

0.29

305

744

0.35

368

849 0.47

494

895 0.54

562

940 0.60

630

1400

577

0.21

221

642

0.27

284

704

0.33

347

766

0.39

410

870 0.52

546

915 0.59

620

959 0.66

693

1500

609

0.26

273

670

0.31

326

729

0.38

394

788

0.44

462

892 0.58

609

936 0.65

683

980 0.72

757

1600

642

0.30

315

699

0.36

378

755

0.43

447

811

0.49

515

913 0.64

672

957 0.72

751

1001 0.79

830

1700

675

0.36

378

728

0.42

441

782

0.49

510

836

0.55

578

935 0.71

746

979 0.79

825

1023 0.86

904

1800

709

0.41

431

759

0.48

504

810

0.55

578

860

0.62

651

957 0.78

820

1001 0.86

904

1044 0.94

988

1900

743

0.48

504

790

0.55

578

838

0.62

651

886

0.69

725

980 0.86

904

1023 0.95

993

1066 1.03

1082

2000

778

0.55

578

836

0.62

651

875

0.70

730

913

0.77

809

1004 0.94

988

1046 1.03

1082

1088 1.12

1177

558D048 (4 TON) (cont)

Airflow

(Cfm)

Alternate Direct-Drive Motor

External Static Pressure (in. wg)

1.0

1.1

1.2

1.4

1.6

1.8

Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts

1200

999 0.66

674 1018 0.67

685 1036 0.68

695 1073 0.71

756 1109 0.75

794 1138 0.79

851

1300

1025 0.74

756 1058 0.79

807 1090 0.84

858 1121 0.87

832 1159 0.90

918 1193 0.95

976

1400

1042 0.81

828 1080 0.88

899

1118 0.95

971 1175 1.06 1014 1206 1.09 1042 1244 1.12 1138

1500

1060 0.88

899 1098 0.96

981 1136 1.04 1063 1205 1.19 1138 1258 1.30 1243 1289 1.34 1282

1600

1080 0.95

971

1117 1.04 1058 1153 1.12 1140 1224 1.29 1234 1287 1.45 1387 1337 1.56 1492

1700

1101 1.03 1053 1137 1.12 1139

1172 1.20 1226 1241 1.38 1320 1307 1.56 1492 1366 1.73 1655

1800

1122 1.11

1134

1157 1.20 1226 1192 1.29 1318 1258 1.48 1415 1323 1.67 1597 1385 1.86 1779

1900

1143 1.21 1237 1179 1.30 1328 1214 1.39 1420 1279 1.58 1511 1341 1.78 1702 1402 1.98 1894

2000

1165 1.31 1339 1200 1.40 1431 1235 1.49 1523 1300 1.69 1616 1361 1.90 1817 1419 2.10 2008

LEGEND

Bhp

Brake Horsepower Input to Fan

FIOP

Factory-Installed Option

Watts — Input Watts to Motor

NOTES:
1. Boldface indicates a field-supplied drive is required. (See Note 7.)

2.

indicates field-supplied motor and drive are required.

3.

indicates maximum usable bhp/watts.

4. Maximum usable watts input is 1000 and maximum continuous bhp

is 1.00. Extensive motor and electrical testing on these units ensures

that the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.

5. Values include losses for filters, unit casing, and wet coils. See

page 47 for accessory/FIOP static pressure information.

6. Use of a field-supplied motor may affect wire sizing. Contact your lo-

cal representative for details.

7. Motor drive range: 835 to 1185 rpm. All other rpms require field-

supplied drive.

8. Interpolation is permissible. Do not extrapolate.
9. Minimum allowable cfm is 300 cfm/ton.

35