AIR DELIVERY — 558D036-150 VERTICAL DISCHARGE UNITS (cont)

558D150 (12

1

2

TON)

Airflow

(Cfm)

Standard and Alernate Belt-Drive Motors

External Static Pressure (in. wg)

0.2

0.4

0.6

0.8

1.0

1.2

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

3750

661

1.16

1097

721

1.36

1255

774

1.55

1415

821

1.72

1556

867

1.90

1709

911

2.13

1905

3800

668

1.20

1129

727

1.40

1291

780

1.60

1456

827

1.77

1598

873

1.95

1751

916

2.18

1948

3900

683

1.28

1194

741

1.49

1365

793

1.70

1540

839

1.88

1691

884

2.05

1836

927

2.28

2035

4000

697

1.37

1267

754

1.59

1448

806

1.80

1624

851

1.99

1785

895

2.16

1931

938

2.38

2123

4100

711

1.46

1340

767

1.69

1531

819

1.90

1708

864

2.10

1879

907

2.28

2035

949

2.49

2219

4200

726

1.56

1423

780

1.80

1624

832

2.01

1802

877

2.22

1983

919

2.41

2149

960

2.60

2316

4300

741

1.66

1506

794

1.91

1717

845

2.12

1897

889

2.35

2096

931

2.54

2263

971

2.72

2433

4400

755

1.77

1598

808

2.03

1819

858

2.24

2000

902

2.48

2210

943

2.68

2387

983

2.86

2548

4500

770

1.89

1700

821

2.15

1923

871

2.37

2114

915

2.61

2325

955

2.82

2512

995

3.01

2683

4600

784

2.00

1794

835

2.27

2027

884

2.49

2219

928

2.75

2450

968

2.96

2638

1006

3.17

2828

4700

799

2.13

1905

849

2.40

2140

897

2.63

2343

941

2.88

2566

981

3.11

2773

1018

3.32

2964

4800

814

2.25

2009

863

2.53

2254

910

2.77

2468

954

3.02

2692

993

3.27

2919

1030

3.48

3111

4900

829

2.39

2131

877

2.67

2378

923

2.92

2602

967

3.17

2828

1006

3.43

3065

1043

3.65

3267

5000

843

2.52

2246

892

2.81

2503

937

3.08

2746

980

3.32

2964

1019

3.60

3221

1055

3.82

3424

5100

858

2.67

2378

906

2.95

2629

950

3.24

2891

993

3.48

3111

1032

3.76

3368

1068

4.00

3590

5200

873

2.82

2512

920

3.10

2764

963

3.40

3037

1006

3.65

3267

1045

3.93

3525

1081

4.19

3767

5300

888

2.97

2647

934

3.26

2910

977

3.57

3193

1019

3.82

3424

1058

4.11

3692

1094

4.38

3943

5400

903

3.13

2792

949

3.43

3065

991

3.75

3359

1032

4.00

3590

1071

4.29

3860

1106

4.57

4120

5500

918

3.30

2946

963

3.59

3212

1004

3.92

3516

1045

4.18

3757

1084

4.47

4027

1119

4.77

4307

5600

933

3.47

3101

978

3.77

3377

1018

4.11

3692

1058

4.38

3943

1097

4.66

4204

1132

4.97

4493

5700

948

3.65

3267

992

3.95

3544

1032

4.30

3869

1072

4.58

4130

1110

4.86

4391

1145

5.18

4689

5800

963

3.83

3433

1006

4.14

3720

1046

4.50

4055

1085

4.79

4326

1123

5.07

4586

1158

5.39

4884

5900

978

4.00

3590

1021

4.34

3906

1060

4.69

4232

1098

5.01

4531

1136

5.28

4782

1171

5.60

5078

6000

993

4.22

3795

1035

4.54

4093

1074

4.91

4419

1112

5.23

4735

1149

5.50

4986

6100

1008

4.42

3981

1050

4.75

4288

1089

5.10

4616

1125

5.45

4939

1162

5.73

5198

6200

1023

4.63

4176

1065

4.96

4484

1103

5.32

4819

1139

5.68

5152

6250

1031

4.74

4279

1072

5.08

4591

1141

5.43

4921

558D150 (12

1

2

TON) (cont)

Airflow

(Cfm)

Standard and Alternate Belt-Drive Motors

External Static Pressure (in. wg)

1.4

1.6

1.8

2.0

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

3750

955

2.33

2075

996

2.53

2251

1035

2.72

2419

1070

2.89

2575

3800

959

2.38

2123

1001

2.58

2299

1040

2.78

2476

1075

2.96

2638

3900

969

2.50

2228

1010

2.70

2405

1049

2.91

2593

1085

3.11

2773

4000

979

2.62

2334

1020

2.83

2521

1059

3.04

2710

1095

3.25

2901

4100

989

2.74

2441

1029

2.96

2638

1068

3.18

2837

1105

3.39

3028

4200

1000

2.86

2548

1039

3.10

2764

1077

3.31

2955

1114

3.54

3166

4300

1011

2.97

2647

1049

3.23

2882

1087

3.46

3092

1124

3.69

3304

4400

1022

3.10

2764

1059

3.37

3010

1097

3.61

3230

1133

3.84

3442

4500

1033

3.23

2882

1070

3.51

3138

1107

3.76

3368

1143

4.00

3590

4600

1044

3.37

3010

1081

3.64

3258

1117

3.92

3516

1152

4.17

3748

4700

1056

3.52

3147

1092

3.78

3387

1127

4.07

3655

1162

4.33

3897

4800

1057

3.69

3304

1103

3.93

3525

1138

4.23

3804

1172

4.50

4055

4900

1079

3.87

3470

1114

4.09

3674

1149

4.37

3934

1182

4.68

4223

5000

1091

4.05

3637

1126

4.25

3822

1160

4.53

4083

1193

4.85

4382

5100

1103

4.23

3804

1137

4.45

4009

1171

4.70

4242

1204

5.01

4531

5200

1115

4.42

3981

1149

4.65

4195

1182

4.91

4409

1215

5.18

4689

5300

1127

4.62

4167

1161

4.85

4382

1194

5.07

4586

1226

5.36

4856

5400

1139

4.82

4354

1173

5.06

4577

1205

5.29

4791

1237

5.55

5032

5500

1152

5.03

4549

1185

5.27

4772

1217

5.51

4995

1248

5.75

5216

5600

1165

5.24

4746

1197

5.49

4976

1229

5.74

5207

5700

1178

5.46

4949

1209

5.72

5189

5800

5900

6000

6100

6200

6250

LEGEND

Bhp

Brake Horsepower Input to Fan

FIOP

Factory-Installed Option

Watts — Input Watts to Motor

NOTES:

1. Boldface indicates a field-supplied or alternate (as appropriate) drive is re-

quired. (See Note 9.)

2.

indicates alternate motor and drive are required.

3.

indicates field-supplied motor and drive are required.

4.

indicates maximum usable bhp/watts of standard motor.

5.

indicates maximum usable bhp/watts of alternate motor.

6. Maximum usable watts input is 3775 with standard motor and 4400 with al-

ternate motor. Maximum continuous bhp is 4.20 with standard motor and 5.25

with alternate motor. Extensive motor and electrical testing on these units en-
sures that the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in nuisance
tripping or premature motor failure. Unit warranty will not be affected. For ad-
ditional information on motor performance, refer to Evaporator-Fan Motor
Performance table on page 62.

7. Values include losses for filters, unit casing, and wet coils. See page 47 for

accessory/FIOP static pressure information.

8. Use of a field-supplied motor may affect wire sizing. Contact your local rep-

resentative for details.

9. Standard motor drive range: 860 to 1080 rpm. Alternate motor drive range:

900 to 1260 rpm. All other rpms require field-supplied drive.

10. Interpolation is permissible. Do not extrapolate.
11. Minimum allowable cfm is 300 cfm/ton.