AIR DELIVERY — 558D036-150 VERTICAL DISCHARGE UNITS (cont)

558D102 (8

1

2

TON)

Airflow

(Cfm)

Standard Belt-Drive Motor

External Static Pressure (in. wg)

0.2

0.4

0.6

0.8

1.0

1.2

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

2550

557

0.71

684

633

0.94

867

697

1.18

1064

756

1.42

1267

811

1.69

1499

861

1.96

1735

2600

565

0.74

708

639

0.97

891

703

1.22

1097

761

1.46

1301

816

1.74

1543

866

2.01

1779

2700

581

0.81

763

652

1.04

948

717

1.31

1173

773

1.55

1378

827

1.83

1621

878

2.12

1875

2800

597

0.89

827

665

1.12

1014

733

1.40

1250

786

1.66

1473

839

1.93

1709

889

2.23

1971

2900

613

0.97

891

679

1.20

1081

745

1.50

1335

799

1.76

1560

850

2.04

1805

900

2.34

2067

3000

629

1.06

965

694

1.29

1156

759

1.59

1413

812

1.88

1665

862

2.15

1901

911

2.46

2171

3100

646

1.15

1039

709

1.39

1241

772

1.70

1508

825

1.99

1761

875

2.28

2015

923

2.58

2275

3200

662

1.25

1123

724

1.50

1335

785

1.80

1595

840

2.11

1866

887

2.41

2128

934

2.71

2386

3300

679

1.35

1207

740

1.61

1430

798

1.91

1691

854

2.24

1980

900

2.54

2240

946

2.85

2504

3400

696

1.46

1301

756

1.73

1534

811

2.02

1788

868

2.37

2093

914

2.69

2369

959

3.00

2629

3500

712

1.57

1396

771

1.85

1639

824

2.14

1892

881

2.50

2206

928

2.84

2495

971

3.16

2759

3600

729

1.69

1499

787

1.98

1753

839

2.27

2006

894

2.64

2326

942

2.99

2620

984

3.32

2886

3700

746

1.82

1613

803

2.12

1875

854

2.42

2136

907

2.78

2445

956

3.15

2751

997

3.49

3017

3750

755

1.89

1674

811

2.20

1945

862

2.49

2197

914

2.85

2504

963

3.23

2815

3800

763

1.95

1726

819

2.27

2006

869

2.56

2257

920

2.92

2562

970

3.31

2878

3900

780

2.09

1849

835

2.42

2136

884

2.72

2394

933

3.07

2686

983

3.48

3009

4000

796

2.23

1971

851

2.56

2257

900

2.89

2537

946

3.23

2815

4100

813

2.39

2110

867

2.74

2411

915

3.06

2678

960

3.40

2948

4200

830

2.55

2249

883

2.91

2554

931

3.24

2823

4250

839

2.63

2317

892

3.00

2629

939

3.34

2902

558D102 (8

1

2

TON) (cont)

Airflow

(Cfm)

Standard Belt-Drive Motor

External Static Pressure (in. wg)

1.4

1.6

1.8

2.0

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

2550

908

2.24

1980

953

2.53

2232

1003

2.87

2521

1045

3.28

2854

2600

913

2.29

2023

957

2.58

2275

1004

2.91

2554

1050

3.31

2878

2700

924

2.40

2120

967

2.70

2377

1010

3.01

2637

1056

3.37

2925

2800

935

2.52

2223

978

2.62

2479

1019

3.13

2735

1061

3.41

3002

2900

946

2.65

2335

989

2.96

2595

1030

3.27

2847

3000

957

2.78

2445

1000

3.09

2702

1040

3.41

2956

3100

968

2.91

2554

1011

3.24

2832

3200

980

3.04

2661

1022

3.38

2933

3300

991

3.18

2775

3400

1003

3.52

2886

3500

1014

3.48

3009

3600

3700

3750

3800

3900

4000

4100

4200

4250

LEGEND

Bhp

Brake Horsepower Input to Fan

FIOP

Factory-Installed Option

Watts — Input Watts to Motor

NOTES:
1. Boldface indicates a field-supplied drive is required. (See Note 7.)

2.

indicates field-supplied motor and drive are required.

3.

indicates maximum usable bhp/watts.

4. Maximum usable watts input is 2120 and maximum continuous bhp

is 2.40. Extensive motor and electrical testing on these units ensures
that the full range of the motor can be utilized with confidence. Using

your fan motors up to the wattage ratings shown will not result in nui-
sance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance refer to
Evaporator-Fan Motor Performance table on page 62.

5. Values include losses for filters, unit casing, and wet coils. See

page 47 for accessory/FIOP static pressure information.

6. Use of a field-supplied motor may affect wire sizing. Contact your lo-

cal representative for details.

7. Motor drive range: 685 to 935 rpm. All other rpms require field-

supplied drive.

8. Interpolation is permissible. Do not extrapolate.
9. Minimum allowable cfm is 300 cfm/ton.

31