AIR DELIVERY — 558D036-150 HORIZONTAL DISCHARGE UNITS (cont)

558D060 (5 TON)

AIRFLOW

(Cfm)

Standard Direct-Drive Motor

Low Speed

Medium Speed

High Speed

208 v

230, 460, 575 v

208 v

230, 460, 575 v

208 v

230, 460, 575 v

ESP

Bhp

Watts

ESP

Bhp

Watts

ESP

Bhp

Watts

ESP

Bhp

Watts

ESP

Bhp

Watts

ESP

Bhp

Watts

1500

1.01

0.67

750

1.25

0.71

791

1.26

0.70

782

1.46

0.76

845

1.46

0.79

875

1.52

0.85

949

1600

0.82

0.70

780

1.09

0.74

824

1.11

0.74

821

1.32

0.79

883

1.33

0.82

913

1.41

0.89

988

1700

0.64

0.73

810

0.97

0.77

857

0.99

0.77

861

1.22

0.83

921

1.24

0.85

950

1.33

0.92

1027

1800

0.44

0.75

839

0.81

0.80

891

0.84

0.80

900

1.09

0.86

959

1.11

0.89

988

1.22

0.96

1066

1900

0.32

0.78

869

0.66

0.83

924

0.69

0.83

940

0.96

0.90

997

0.99

0.92

1025

1.11

0.99

1105

2000

0.21

0.81

899

0.47

0.86

957

0.51

0.86

979

0.80

0.93

1035

0.83

0.95

1063

0.97

1.03

1144

2100

0.13

0.83

929

0.32

0.89

990

0.36

0.89

1018

0.64

0.96

1073

0.71

0.99

1101

0.86

1.06

1183

2200

0.05

0.86

959

0.19

0.92

1023

0.21

0.92

1058

0.50

1.00

1111

0.58

1.02

1138

0.75

1.10

1222

2300

0.08

0.95

1057

0.08

0.95

1097

0.34

1.03

1149

0.39

1.06

1176

0.57

1.13

1261

2400

0.24

1.07

1187

0.29

1.09

1213

0.49

1.17

1300

2500

0.15

1.10

1225

0.15

1.12

1251

0.34

1.20

1340

LEGEND

Bhp

Brake Horsepower Input to Fan

ESP

External Static Pressure (in. wg)

FIOP

Factory-Installed Option

Watts — Input Watts to Motor

NOTES:
1. Values include losses for filters, unit casing, and wet coils. See

page 47 for accessory/FIOP static pressure information.

2. Extensive motor and electrical testing on these units ensures that the

full range of the motor can be utilized with confidence. Using

your fan motors up to the wattage ratings shown will not result in nui-
sance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.

3. Use of a field-supplied motor may affect wire sizing. Contact your lo-

cal representative for details.

4. Minimum allowable cfm is 300 cfm/ton.

558D060 (5 TON)

Airflow

(Cfm)

Alternate Belt-Drive Motor

External Static Pressure (in. wg)

0.1

0.2

0.4

0.6

0.8

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1500

658

0.27

276

722

0.33

337

840

0.46

470

937

0.59

603

1027

0.74

756

1600

693

0.32

327

754

0.38

388

867

0.52

531

963

0.65

664

1052

0.81

828

1700

729

0.38

388

787

0.44

450

895

0.58

593

991

0.73

746

1075

0.88

899

1800

765

0.45

460

821

0.51

521

923

0.65

664

1019

0.81

828

1099

0.96

981

1900

802

0.52

531

854

0.58

593

953

0.73

746

1046

0.90

920

1126

1.06

1083

2000

840

0.60

613

900

0.66

674

984

0.82

838

1073

0.99

1012

1154

1.16

1185

2100

878

0.69

705

923

0.75

766

1015

0.91

930

1101

1.08

1104

1182

1.27

1298

2200

916

0.78

797

958

0.85

869

1046

1.01

1032

1129

1.19

1216

1209

1.39

1420

2300

954

0.89

910

993

0.96

981

1079

1.13

1155

1160

1.31

1339

1237

1.51

1543

2400

993

1.00

1022

1029

1.07

1093

1112

1.25

1277

1190

1.43

1461

1264

1.63

1666

2500

1031

1.13

1155

1066

1.20

1226

1145

1.39

1420

1220

1.57

1604

1292

1.77

1809

558D060 (5 TON) (cont)

Airflow

(Cfm)

Alternate Belt-Drive Motor

External Static Pressure (in. wg)

1.0

1.2

1.4

1.6

1.8

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1500

1108

0.90

920

1186

1.08

1104

1263

1.30

1328

1343

1.58

1615

1431

1.79

1829

1600

1130

0.97

991

1205

1.15

1175

1278

1.35

1380

1350

1.61

1645

1424

1.80

1921

1700

1154

1.06

1083

1226

1.23

1257

1296

1.42

1451

1364

1.64

1676

1432

1.89

1931

1800

1178

1.14

1165

1249

1.32

1349

1316

1.52

1553

1382

1.72

1758

1447

1.95

1993

1900

1201

1.23

1257

1274

1.43

1461

1338

1.62

1656

1402

1.80

1870

1464

2.05

2095

2000

1226

1.33

1359

1297

1.53

1564

1363

1.73

1768

1424

1.94

1983

1484

2.16

2207

2100

1252

1.45

1482

1320

1.64

1676

1388

1.80

1891

1448

2.07

2115

1505

2.29

2340

2200

1280

1.58

1615

1345

1.77

1809

1410

1.97

2013

1473

2.20

2248

1529

2.43

2483

2300

1309

1.71

1747

1372

1.91

1952

1434

2.11

2156

1496

2.34

2391

1554

2.58

2637

2400

1336

1.80

1891

1400

2.06

2105

1459

2.26

2310

1519

2.48

2534

1578

2.76

2820

2500

1363

2.00

2044

1428

2.22

2269

1486

2.43

2483

1543

2.65

2708

1600

2.89

2953

LEGEND

Bhp

Brake Horsepower Input to Fan

FIOP

Factory-Installed Option

Watts — Input Watts to Motor

NOTES:
1. Boldface indicates a field-supplied drive is required. (See Note 7.)

2.

indicates field-supplied motor and drive are required.

3.

indicates maximum usable bhp/watts.

4. Maximum usable watts input is 1921 and maximum continuous bhp

is 1.80. Extensive motor and electrical testing on these units ensures
that the full range of the motor can be utilized with confidence. Using

your fan motors up to the wattage ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.

5. Values include losses for filters, unit casing, and wet coils. See

page 47 for accessory/FIOP static pressure information.

6. Use of a field-supplied motor may affect wire sizing. Contact your lo-

cal representative for details.

7. Motor drive range: 900 to 1300 rpm. All other rpms require field-

supplied drive.

8. Interpolation is permissible. Do not extrapolate.
9. Minimum allowable cfm is 300 cfm/ton.