AIR DELIVERY — 558D036-150 VERTICAL DISCHARGE UNITS (cont)

558D048 (4 TON)

Airflow

(Cfm)

Standard Direct-Drive Motor

Low Speed

High Speed

208 v

230, 460, 575 v

208 v

230, 460, 575 v

ESP

Bhp

Watts

ESP

Bhp

Watts

ESP

Bhp

Watts

ESP

Bhp

Watts

1200

0.93

0.41

458

0.94

0.45

506

0.94

0.51

572

0.99

0.56

632

1300

0.86

0.42

471

0.87

0.46

521

0.87

0.52

589

0.92

0.58

651

1400

0.78

0.45

503

0.79

0.49

556

0.79

0.54

616

0.87

0.60

681

1500

0.70

0.47

536

0.73

0.52

593

0.73

0.56

631

0.80

0.62

698

1600

0.61

0.49

557

0.64

0.54

616

0.66

0.58

654

0.76

0.64

723

1700

0.51

0.52

584

0.54

0.57

646

0.58

0.60

678

0.68

0.66

750

1800

0.40

0.54

610

0.44

0.60

674

0.51

0.62

698

0.63

0.68

772

1900

0.29

0.56

629

0.37

0.62

696

0.46

0.64

720

0.56

0.70

796

2000

0.25

0.58

651

0.30

0.64

720

0.39

0.66

744

0.50

0.73

823

LEGEND

Bhp

Brake Horsepower Input to Fan

ESP

External Static Pressure (in. wg)

FIOP

Factory-Installed Option

Watts — Input Watts to Motor

NOTES:
1. Values include losses for filters, unit casing, and wet coils. See

page 47 for accessory/FIOP static pressure information.

2. Extensive motor and electrical testing on these units ensures that the

full range of the motor can be utilized with confidence. Using

your fan motors up to the wattage ratings shown will not result in nui-
sance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.

3. Use of a field-supplied motor may affect wire sizing. Contact your lo-

cal representative for details.

4. Minimum allowable cfm is 300 cfm/ton.

558D048 (4 TON)

Airflow

(Cfm)

Alternate Belt-Drive Motor

External Static Pressure (in. wg)

0.1

0.2

0.3

0.4

0.6

0.7

0.8

Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts

1200

542

0.16

168

616

0.21

221

678

0.27

278

739

0.32

336

842 0.44

462

886 0.50

525

929 0.56

588

1300

576

0.20

210

644

0.25

263

704

0.31

326

764

0.37

389

867 0.50

525

910 0.56

588

952 0.62

651

1400

610

0.24

252

673

0.30

315

732

0.36

378

791

0.42

441

889 0.55

578

933 0.62

651

976 0.69

725

1500

646

0.28

294

704

0.35

368

761

0.42

436

818

0.48

504

912 0.61

641

957 0.69

720

1001 0.76

777

1600

681

0.33

347

735

0.40

420

790

0.47

494

845

0.54

567

920 0.68

695

931 0.76

772

1023 0.83

848

1700

718

0.39

410

768

0.46

483

836

0.54

562

873

0.61

641

965 0.76

777

1005 0.84

853

1045 0.91

930

1800

754

0.45

473

801

0.53

557

851

0.61

641

900

0.69

725

992 0.84

858

1032 0.92

940

1071 1.00

1022

1900

791

0.52

546

836

0.60

630

832

0.69

720

828

0.77

809

1019 0.93

950

1058 1.02

1037

1097 1.10

1124

2000

828

0.60

630

870

0.68

714

864

0.77

809

858

0.86

904

1046 1.03

1053

1085 1.12

1139

1124 1.21

1237

558D048 (4 TON) (cont)

Airflow

(Cfm)

Alternate Belt-Drive Motor

External Static Pressure (in. wg)

1.0

1.1

1.2

1.4

1.6

1.8

Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts

1200

1008 0.67

704

1052 0.73

762

1096 0.78

820

1134 0.89

835

1203 1.00

885

1300

1029 0.75

788

1065 0.81

846

1101 0.86

904

1174 1.01

1040

1229 1.15

1100

1277 1.27

1029

1400

1052 0.83

826

1087 0.90

890

1121 0.96

918

1183 1.09

1042

1255 1.22

1167

1305 1.38

1190

1500

1076 0.91

905

1111 0.99

980

1145 1.06

1014

1208 1.20

1138

1274 1.33

1272

1337 1.47

1350

1600

1100 1.00

995

1134 1.08

1069

1168 1.15

1100

1232 1.31

1253

1291 1.46

1396

1350 1.60

1558

1700

1124 1.09

1084

1158 1.17

1164

1192 1.25

1196

1255 1.42

1358

1314 1.58

1511

1370 1.77

1738

1800

1147 1.18

1174

1182 1.27

1263

1217 1.36

1301

1279 1.54

1473

1381 1.71

1635

1393 1.89

1907

1900

1169 1.27

1263

1205 1.37

1363

1240 1.47

1406

1303 1.66

1588

1408 1.85

1769

1417 2.03

2068

2000

1194 1.38

1373

1228 1.48

1472

1262 1.58

1511

1327 1.78

1702

1436 1.98

1894

1440 2.18

2229

LEGEND

Bhp

Brake Horsepower Input to Fan

FIOP

Factory-Installed Option

Watts — Input Watts to Motor

NOTES:
1. Boldface indicates a field-supplied drive is required. (See Note 7.)

2.

indicates field-supplied motor and drive are required.

3.

indicates maximum usable bhp/watts.

4. Maximum usable watts input is 1000 and maximum continuous bhp

is 1.00. Extensive motor and electrical testing on these units ensures
that the full range of the motor can be utilized with confidence. Using

your fan motors up to the wattage ratings shown will not result in nui-
sance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.

5. Values include losses for filters, unit casing, and wet coils. See

page 47 for accessory/FIOP static pressure information.

6. Use of a field-supplied motor may affect wire sizing. Contact your lo-

cal representative for details.

7. Motor drive range: 835 to 1185 rpm. All other rpms require field-

supplied drive.

8. Interpolation is permissible. Do not extrapolate.
9. Minimum allowable cfm is 300 cfm/ton.

27