ELECTRIC HEATER CAPACITIES — 558D036-150

UNIT
558D

VOLTAGE

(60 Hz)

ACCESSORY

kW

036

208/230

(single phase)

4.4
6.5
8.7

10.5

13.0*

208/230

(3 phase)

4.4
6.5
8.7

10.5
16.0

460

(3 phase)

6.0
8.8

11.5

14.0

048

208/230

(single phase)

4.4
8.7

13.0*
17.4*
21.0*

208/230

(3 phase)

6.5
8.7

16.0

21.0*

460

(3 phase)

6.0

11.5

14.0*
23.0*

060

208/230

(single phase)

6.5
8.7

13.0*
17.4*
21.0*

208/230

(3 phase)

6.5

10.5
16.0

21.0*
26.5*

460

(3 phase)

6.0

11.5

14.0

23.0*
25.0*

072

208/230

(3 phase)

6.5

10.5
16.0

21.0*
26.5*

460

(3 phase)

6.0

11.5

14.0

23.0*
25.5*

ELECTRIC HEATER CAPACITIES —

558D036-150 (cont)

UNIT
558D

VOLTAGE

(60 Hz)

ACCESSORY

kW

090,102

208/230

(3 phase)

10.4
16.0
24.8
32.0

42.4*

460

(3 phase)

13.9
16.5
27.8
33.0

41.7*

575

(3 phase)

18.0
36.0

120,150

208/230

(3 phase)

10.4
16.0
32.0

42.4*
50.0*

460

(3 phase)

16.5
27.8
33.0

41.7*
50.0*

575

(3 phase)

18.0
36.0

54.0*

*Two heater packages required to provide kW indicated.

NOTES:
1. The kW ratings shown above are at 240, 480, and 575 v. Use the

Electric Heat Multiplication Factors table on page 48 to determine
heater capacity for your particular voltage.

2. Heaters are not available for size 036-072, 575-v units.

ELECTRIC RESISTANCE HEATER DATA — 559F180-300

UNIT
559F

HEATER kW

HEATER
STAGES

% HEAT

PER STAGE

MAXIMUM

STAGES*

Unit Voltages

208

230

460

575

180

26

34

32

2

50/50

2

42

56

55

2

33/67

3

56

75

80

50

2

50/50

4

216-300

26

34

32

2

50/50

2

42

56

55

2

33/67

3

56

75

80

2

50/50

4

*Maximum number of stages using accessory low-ambient kit or head pressure control device and low-

ambient kit.

NOTE: Heaters are rated at 240 v, 480 v, and 575 v.