Bryant 558F User Manual

Page 50

Advertising
background image

ELECTRICAL DATA — 558D036-072 (cont)

UNIT
558D

NOMINAL

V-PH-Hz

IFM

TYPE

VOLTAGE

RANGE

COMPR

(each)

OFM

IFM

ELECTRIC

HEAT*

POWER SUPPLY

DISCONNECT

SIZE†

Min

Max

RLA

LRA

Quantity

Hp

FLA

FLA

Nom kW**

FLA

MCA

MOCP††

FLA

LRA

060

(5 Ton)

208/230-1-60

Std

187

254

28.3

141

1

1

4

1.4

5.9

42.7/ 42.7

50/ 50

43/ 43

155/155

4.9/ 6.5

23.5/27.1

42.7/ 42.7

50/ 50

43/ 43

6.5/ 8.7

31.4/36.3

46.6/ 52.7

50/ 60

46/ 49

9.8/13.0

46.9/54.2

66.0/ 75.1

70/ 80

64/ 69

13.0/17.4

62.8/72.5

85.9/ 98.0

90/100

82/ 90

15.8/21.0

75.8/87.5

102.2/116.8

110/125

97/107

Alt

8.5

48.3/ 48.3

60/ 60

47/ 47

178/178

4.9/ 6.5

23.5/27.1

48.3/ 48.3

60/ 60

47/ 47

6.5/ 8.7

31.4/36.3

50.3/ 56.3

60/ 60

47/ 52

9.8/13.0

46.9/54.2

69.7/ 78.7

70/ 80

64/ 72

13.0/17.4

62.8/72.5

89.5/101.6

90/110

82/ 93

15.8/21.0

75.8/87.5

105.8/120.4

110/125

97/111

208/230-3-60

Std

187

254

17.7

110

1

1

4

1.4

5.9

29.4/ 29.4

35/ 35

29/ 29

124/124

4.9/ 6.5

13.6/15.6

29.4/ 29.4

35/ 35

29/ 29

7.9/10.5

21.9/25.3

34.7/ 38.9

40/ 40

32/ 36

12.0/16.0

33.4/38.5

49.1/ 55.5

50/ 60

46/ 51

15.8/21.0

43.8/50.5

62.1/ 70.5

70/ 80

57/ 65

19.9/26.5

55.2/63.8

76.4/ 87.1

80/ 90

70/ 80

Alt

8.5

32.0/ 32.0

40/ 40

29/ 29

145/145

4.9/ 6.5

13.6/15.6

32.0/ 32.0

40/ 40

29/ 29

7.9/10.5

21.9/25.3

38.0/ 42.2

45/ 45

32/ 36

12.0/16.0

33.4/38.5

52.3/ 58.7

60/ 60

45/ 51

15.8/21.0

43.8/50.5

65.3/ 73.8

70/ 80

57/ 65

19.9/26.5

55.2/63.8

79.7/ 90.3

80/100

70/ 80

460-3-60

Std

414

508

8.6

55

1

1

4

0.8

3.2

14.8

20

15

63

6.0

7.2

14.8

20

15

11.5

13.8

21.3

25

20

14.0

16.8

25.0

30

23

23.0

27.7

38.6

40

36

25.0

30.1

41.6

45

38

Alt

4.5

16.1

20

14

73

6.0

7.2

16.1

20

14

11.5

13.8

22.9

25

19

14.0

16.8

26.7

30

22

23.0

27.7

40.2

45

35

25.0

30.1

43.2

45

38

575-3-60

Std

518

632

6.4

44

1

1

4

0.8

3.2

12.0

15

12

52

Alt

2.6

11.4

15

12

62

072

(6 Ton)

208/230-

3-60

Std

187

254

20.9

142

1

1

4

1.4

5.8

33.3/ 33.3

40/ 40

32/ 32

187/187

4.9/ 6.5

13.6/15.6

33.3/ 33.3

40/ 40

32/ 32

7.9/10.5

21.9/25.3

33.3/ 38.8

40/ 40

32/ 36

12.0/16.0

33.4/38.4

48.9/ 55.4

50/ 60

45/ 51

15.8/21.0

43.8/50.5

62.0/ 70.4

70/ 80

57/ 65

19.9/26.5

55.2/63.8

76.8/ 86.9

80/ 90

70/ 80

460-3-60

Std

414

508

9.9

72

1

1

4

0.8

2.6

15.6

20

15

94

6.0

7.2

15.6

20

15

11.5

13.8

20.5

25

19

14.0

16.8

24.3

25

22

23.0

27.8

37.8

40

35

25.5

30.7

41.6

45

38

575-3-60

Std

518

632

7.9

58

1

1

4

0.8

2.6

14.6

15

12

76

LEGEND AND NOTES FOR ELECTRICAL DATA TABLES ON PAGES 49-54

LEGEND

FLA

Full Load Amps

HACR

Heating, Air Conditioning and Refrigeration

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v, and

575 v. Heaters are rated at 240 v, 480 v, and 575 v. If power distribution voltage to unit
varies from rated heater voltage, heater kW will vary accordingly. To determine heater
capacity at actual unit voltage, multiply 240 v, 480 v, or 575 v capacity by multipliers
found in Electric Heat Multiplication Factors table on page 48.

†Used to determine minimum disconnect size per NEC.

**Heaters are field installed only.

††Fuse or HACR circuit breaker.

Fusing in single point box provides the required branch circuit protection.

NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment

(refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall
be fuse or HACR breaker. The Canadian units may be fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than
2%. Use the following formula to determine the percent of voltage imbalance.

max voltage deviation from average voltage

% Voltage Imbalance =100 x

average voltage

EXAMPLE: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3

= 457

Determine maximum deviation from average voltage.

(AB) 457 − 452 = 5 v
(BC) 464 − 457 = 7 v
(AC) 457 − 455 = 2 v

Maximum deviation is 7 v.
Determine percent of voltage imbalance.

7

% Voltage Imbalance = 100 x

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your
local electric utility company immediately.

3. MCA calculation for 558F180-300 units with electric heaters over 50 kW =

(1.25 x IFM amps) + (1.00 x heater FLA).

036-150 Only

036-072 Only

090-150 Only

180-300 Only

180-300 Only

50

Advertising
This manual is related to the following products: