Bryant 558F User Manual

Page 9

Advertising
background image

DIMENSIONAL DRAWING — 559F240,300

NOTES:
1. Dimensions in (

) are in millimeters.

2.

Center of gravity.

3.

Direction of airflow.

4. Ductwork to be attached to accessory roof curb or adapter

only.

5. For units with electric heat, a field-supplied 90° elbow must

be installed in the supply ductwork below the unit discharge
connection.

6. Minimum clearance:

a. Rear: 7

Ј

-0

Љ

(2134) for coil removal. This dimension can

be reduced to 4

Ј

-0

Љ

(1219) if conditions permit coil re-

moval from the top.

b. Left side: 4

Ј

-0

Љ

(1219) for proper condenser coil airflow.

c. Front: 4

Ј

-0

Љ

(1219) for control box access.

d. Right side: 4

Ј

-0

Љ

(1219) for proper operation of damper

and power exhaust if so equipped.

e. Top: 6

Ј

-0

Љ

(1829) to assure proper condenser fan

operation.

f. Local codes or jurisdiction may prevail.

7. With the exception of clearance for the condenser coil and

the damper/power exhaust as stated in note no. 6, remov-
able fence or barricade requires no clearance.

8. Dimensions are from outside of corner post. Allow 0

Ј

-

5

16

Љ

(8)

on each side for top panel drip edge.

UNIT
559F

CORNER WEIGHT*

A

B

C

D

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

240

497

225

470

213

461

209

672

305

300

513

233

532

241

542

246

563

255

*Weights are for unit only and do not include options or crating.

UNIT
559F

DIMENSIONS

X

Y

Ft-in.

mm

Ft-in.

mm

240

3-7

1092

3-2

965

300

3-5

1035

3-7

1092

9