ELECTRICAL DATA — 559F180-300 UNITS (cont)

UNIT
559F

NOMINAL

V-PH-Hz

VOLTAGE

RANGE

COMPRESSOR

OFM

IFM

POWER

EXHAUST

ELECTRIC

HEAT*

POWER

SUPPLY

No. 1

No. 2

Min

Max

RLA

LRA

RLA

LRA

Quantity

Hp

FLA

(ea)

FLA

FLA

LRA

FLA

Nom kW**

MCA

MOCP††

240

208/230-3-60

187

254

35.6

198

35.6

198

2

1

5.50

25.0/25.0

—/—

—/—

116/116

150/150

72/ 82

26/34

121/134

150/150

117/135

42/56

178/166

200/175

156/180

56/75

187/211

200/225

4.6

18.8

—/—

—/—

121/121

150/150

72/ 82

26/34

127/140

150/150

117/135

42/56

183/172

200/175

156/180

56/75

193/217

200/225

460-3-60

414

508

17.8

99

17.8

99

2

1

2.80

13.0

59

70

39

32

65

70

66

55

82

90

96

80

112

125

2.3

6.0

61

70

39

32

68

70

66

55

85

90

96

80

115

125

575-3-60

518

632

14.3

79

14.3

79

2

1

3.40

10.0

49

60

2.1

4.8

51

60

300

208/230-3-60

187

254

43.6

228

43.6

228

2

1

5.50

28.0/28.0

—/—

—/—

137/137

175/175

72/ 82

26/34

137/138

175/175

117/135

42/56

181/170

200/175

156/180

56/75

191/215

200/225

4.6

18.8

—/—

—/—

142/142

175/175

72/82

26/34

142/143

175/175

117/135

42/56

187/176

200/200

156/180

56/75

197/221

200/225

460-3-60

414

508

22.1

114

22.1

114

2

1

2.80

14.6

70

90

39

32

70

90

66

55

84

90

96

80

114

125

2.3

6.0

72

90

39

32

72

90

66

55

87

90

96

80

117

125

575-3-60

518

632

17.9

91

17.9

91

2

1

3.40

13.0

60

70

2.1

4.8

62

80

LEGEND AND NOTES FOR ELECTRICAL DATA TABLES ON PAGES 49-54

LEGEND

FLA

Full Load Amps

HACR

Heating, Air Conditioning and Refrigeration

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v, and

575 v. Heaters are rated at 240 v, 480 v, or 575 v. If power distribution voltage
to unit varies from rated heater voltage, heater kW will vary accordingly. To de-
termine heater capacity at actual unit voltage, multiply 240 v, 480 v, or 575 v
capacity by multipliers found in Electric Heat Multiplication Factors table on
page 48.

†Used to determine minimum disconnect size per NEC.

**Heaters are field installed only.

††Fuse or HACR circuit breaker.

Fusing in single point box provides the required branch circuit protection.

NOTES:
1. In compliance with NEC requirements for multimotor and combination load

equipment (refer to NEC Articles 430 and 440), the overcurrent protective de-
vice for the unit shall be fuse or HACR breaker. The Canadian units may be
fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater
than 2%.

Use the following formula to determine the percent of voltage

imbalance.

max voltage deviation from average voltage

% Voltage Imbalance = 100 x

average voltage

EXAMPLE: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3

= 457

Determine maximum deviation from average voltage.

(AB) 457 − 452 = 5 v
(BC) 464 − 457 = 7 v
(AC) 457 − 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

7

% Voltage Imbalance = 100 x

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact
your local electric utility company immediately.

3. MCA calculation for units with electric heaters over 50 kW = (1.25 x IFM amps)

+ (1.00 x heater FLA).

036-150 Only

036-072 Only

090-150 Only

180-300 Only

180-300 Only

54