6.3 Pipe length and the elevation

The pipe length and refrigerant amount:

Model

Connective

pipe length

Air purging method

Additional amount of refrigerant to be charged

All

Less than 5m

Use vacuum pump

------------------

9K/12K

More than 5m

Use vacuum pump

(Pipe length – 5) × 20g/m

18K/24K More than 5m

Use vacuum pump

(Pipe length – 5) × 40g/m

Model

Standard

length

(m)

Max.

Elevation

B (m)

Max.

Length

A (m)

9K/12K

5

8

20

18K/24K

5

10

25

Caution:

Capacity test is based on standard length and maximum allowance length is based on system

reliability.

Oil trap should be installed per 5-7 meters.