Klimaire KSIL024-H219 Service Manual User Manual

Page 44

Advertising
background image

42

I3HEAT

I2HEAT

I1HEAT

Off

Decrease

Hold

Resume

Off: Compressor stops.

Decrease: Decrease the running frequency to the lower level.

Hold: Keep the current frequency.

Resume: No limitation for frequency.

Note:

When AC is in “hold” zone for 3 minutes, the compressor frequency will rise to the higher level. (The

frequency will increase twice at most)

8.4.3.2 Outdoor fan running rules:

17

15

Low

High