8.4.3 Heating Mode

8.4.3.1 Compressor running rules:

The maximum operation frequency of the compressor after starting submits to the following rule.

Fmax=F3

Fmax=F5

Fmax=F7

Fmax=F9

Fmax=F10

Fmax=F8

Fmax=F6

Fmax=F2

34

Off

33

28
27

25

24

22
21

19

18

16

17

15

14

Fmax=F4

12
11

6

5

If users switch on AC by remote controller, the compressor will run at the Fmax frequency for 7

minutes according to outdoor ambient temp. During the 7 minutes, the frequency limitation is active.

7 minutes later, the compressor running frequency will be controlled as below: