Klimaire KSIL024-H219 Service Manual User Manual

Page 43

Advertising
background image

41

+5.0

+4.5

+3.5

+3.0

+2.5

+2.0

+1.5

+1.0

H

G

H

F

E

D

C

B

A

+0.5

While

Temp. zone

A

B

C

D

E

F

G

Frequency

F10

F9

F8

F7

F5

F3

F1

T=0 as factory setting.

Note:

When T1-Ts keeps in the same temp. zone for 3 minutes, the compressor will run as the below rules:

A~E: Increase the frequency to the higher level until to F10.

F: Keep the current frequency.

G: Decrease the frequency to the lower level until to F1.

H: Run at F1 for 1h.(if T1-Ts-

T >11 ºF, the compressor will stop)

Meanwhile, the compressor running frequency is limited by the current.