9.2.2 Indoor unit and outdoor unit communication protection error diagnosis and solution

No

Yes

Yes

No

Yes

The unit does not work normally

Check the wiring between indoor and outdoor

unit. Is the connection of L, N, S and GND good?

No

Is the LED4(red) bright and LED1(yellow)

blinking on outdoor PCB?

The power supply for outdoor PCB is fail.

Check the wiring on outdoor PCB

comparing with wiring plate. Is the

connection good?

The unit does not

work normally

Turn off the power supply, after 1 minute, connect the

power supply, turn on the unit with remote controller

Replace indoor PCB and repower

Replace outdoor e-box.

Correct the connection

Reconnect and retest

Replace the outdoor e-box