9.2.5 IGBT over-strong current protection diagnosis and solution

9.2.6 Over voltage or too low voltage protection diagnosis and solution

9.2.7 High temperature protection of compressor top diagnosis and solution

Yes

Yes

No,

Charge refrigerant

Is the abnormality the same

after gas charging?

Replace the outdoor PCB.

No

Yes

Is protector normal?

No

No

Is the connection good?

Is refrigerant circulation

volume normal?

Reconnect it

Does the compressor operate?

Replace it

Is the power supply good?

Replace the outdoor e-box.

Make sure the power supply is normal.

Yes

No

Yes

Fastening the IPM to the radiator

No

Check whether the connections between

outdoor PCB and IPM are good?

Check whether the IPM is fixed to radiator

tightly

Replace the IPM

The unit does not work normally

Replace the compressor

There is block (Such as capillary or

welded points of the pipes.)