8.4.3.3 Indoor fan running rules:

44

38
37

34

33

Setting

Low

Breeze

Off

17

If the compressor stops caused by the room temperature rising, the indoor fan will be forced to run 127

seconds with breeze. During this period, the anti-cold-wind is disabled.

If the machine runs in rating capacity test mode, the indoor fan will run with rating speed and the

anti-cold-wind function is disabled.

Indoor fan speed can be set as high, medium, low or auto fan and the anti-cold-wind function is

preferential.

Auto fan action in heating mode:

2.5

2

High

Low

1

Medium

1.5

8.4.3.4 Defrosting mode

Condition of defrosting:

----T4

32 ºF,

When the units are running, if the following two items are satisfied, the units start defrosting:

The units run with T3

37 ºF for 40 minutes and T3 keeps lower than TCDI 1.8 ºF for more than 3

minutes.