8.4.2.4 Condenser high temperature T3 protection.
---131 ºF <T3<140 ºF, the compressor frequency will decrease to the lower level until to F1 and then
runs at F1.If T3<129 ºF, the compressor will keep running at the current frequency.
---T3<126 ºF, the compressor will not limit the frequency and resume to the former frequency.
---T3>140 ºF for 5 seconds, the compressor will stop until T3<126 ºF.
8.4.2.5 Evaporator low temperature T2 protection.
---T2<32 ºF, the compressor will stop and restart when T2
>=41 ºF
.
---32 ºF
≦
T2<39 ºF, the compressor frequency will be limited and decreased to the lower level
---39 ºF
≤
T2
≤
45 ºF, the compressor will keep the current frequency.
---T2>45 ºF, the compressor frequency will not be limited.