8.4.2.4 Condenser high temperature T3 protection.

---131 ºF <T3<140 ºF, the compressor frequency will decrease to the lower level until to F1 and then

runs at F1.If T3<129 ºF, the compressor will keep running at the current frequency.

---T3<126 ºF, the compressor will not limit the frequency and resume to the former frequency.

---T3>140 ºF for 5 seconds, the compressor will stop until T3<126 ºF.

8.4.2.5 Evaporator low temperature T2 protection.

---T2<32 ºF, the compressor will stop and restart when T2

>=41 ºF

.

---32 ºF

T2<39 ºF, the compressor frequency will be limited and decreased to the lower level

---39 ºF

T2

45 ºF, the compressor will keep the current frequency.

---T2>45 ºF, the compressor frequency will not be limited.