Klimaire KSIL024-H219 Service Manual User Manual

Page 55

Advertising
background image

53

9.2.3 Fan speed has been out of control diagnosis

9.2.4 Open or short circuit of temperature sensor diagnosis and solution

Yes

Replace the outdoor PCB

Yes

Check the connections between

the sensors and the PCB. Are the

connections good?

Replace the sensor and check if

the errors happen again?

Is the fan motor connector and

connection good?

The unit does not work normally

Turn off the unit, rotate the cross

fan. Does it rotate freely?

No

Disassemble the connection between

fan and motor, check if the bearing is

normal. If not, change the bearing. If

yes, follow the below step.

Yes

No

Yes

Is the voltage being applied to the fan

motor?

Yes

Shut off the power supply and turn on it 5s later

Replace the fan motor

Replace the PCB