The units run with T3

37 ºF for 80 minutes and T3 keeps lower than TCDI +35.6 ºF for more than 3

minutes. While TCDI

=

21 ºF.

----T4

32 ºF,

If the 1

st

condition and 2

nd

condition items are satisfied, then the program judges if T2 has decreased

more than 9 ºF. When T2 has decreased more than 9ºF, enters the defrosting mode.

----No matter what value T4 is, if the machine runs with T3

37 ºF for more than 120 minutes and T3

keeps lower than TCDI 39ºF for more than 3 minutes, the machine will enter defrosting mode no

matter if T2 drops more than 41 ºF or not.

Condition of ending defrosting:

If any one of the following items is satisfied, the defrosting will finish and the machine will turn to

normal heating mode.

----T3 rises to be higher than TCDE 34 ºF.

----T3 keeps being higher than TCDE 35.6 ºF for 80 seconds.

----The machine has run for 10 minutes in defrosting mode.

While TCDE1=27 ºF, TCDE2=14.4 ºF for 18k, 24k models. TCDE1=21.6 ºF, TCDE2=14.4 ºF for other

models.