Fx status warn(ing) screens, Warn(ing) screens – Outback Power Systems MATE2 User Manual

Page 45

Advertising
background image



FX STATUS WARN(ING) Screens

STATUS/FX/PAGE2-----------------

choose category:

PG1 ERROR WARN PG3

STATUS/FX/WARN-------------P00

acin freq No

too low
DOWN UP TOP PORT

STATUS/FX/WARN-------------P00

acin freq No

too high
DOWN STATUS PORT

STATUS/FX/WARN--------------P00

acin voltage No

too high
DOWN UP TOP PORT

STATUS/FX/WARN-------------P00

acin input No

current exceeds max
DOWN UP TOP PORT

STATUS/FX/WARN-------------P00

acin voltage No

too low
DOWN UP TOP PORT

STATUS/FX/WARN-------------P00

temperature No

sensor fault
DOWN UP TOP PORT

STATUS/FX/WARN--------------P00

internal fan No

failure detected
DOWN UP TOP PORT

STATUS/FX/WARN-------------P00

internal comm No

error detected
DOWN UP TOP PORT

STATUS/FX/WARN------------P00

airtemp 190

DOWN UP PORT

STATUS/FX/WARN-----------P00

captemp 186

DOWN UP PORT

STATUS/FX/WARN-----------P00

fettemp 184

DOWN UP PORT

STATUS/FX/WARN------------------

end of warnings menu

UP TOP STATUS

STATUS/FX/PAGE3-----------------

choose category:

PG2 DISCON SELL MAIN

STATUS/FX/PAGE2------------------

choose category:

PG1 ERROR WARN PG3

WARN(ING) Screens

acin freq too high: AC source is above 66 Hz (upper limit) and will be dropped if frequency gets much higher

acin freq too low: AC source is under 54 Hz (lower limit) and will be dropped if frequency gets much lower

acin voltage too high: AC source’s voltage is over 140 VAC (default limit) and risks loss of FX connection

acin voltage too low: AC source’s voltage is under 108 VAC (default limit) and risks loss of FX connection

acin input current exceeds max: AC loads are drawing more current than the rating of the FX allows

temperature sensor fault: an internal FX temperature sensor is malfunctioning

internal comm. error detected: there is a communication problem between the MATE and the FX

internal fan failure detected: the FX’s internal cooling fan is not operating properly

airtemp: displays a numeric value representing the air temperature around the FX*

fettemp: displays a numeric value representing the temperature of the FETs (Field Effect Transistors)*

captemp: displays a numeric value representing the temperature of the ripple capacitors*

*These values are used for troubleshooting purposes. The higher the numerical value, the cooler the temperature.