HBX-Drop Grid Set Point

HBX-Drop Grid Delay

ADV/MATE/HBX---------------------

hbx-drop 26.0 vdc

grid set point
DOWN UP INC DEC

ADV/MATE/HBX---------------------

hbx-drop 01.0 hrs

grid delay
DOWN UP INC DEC

This set point shows the voltage—26.0 VDC

is the default for a 24V system—at which the

FX will DROP its AC input source. The battery

voltage must remain above this voltage for the

amount of time set by HBX-DROP GRID DELAY

(next screen) for a DROP to be issued. Press the

<DOWN> soft key to proceed.

This set point is the amount of time—01.0 hrs in

this case—battery voltage must remain above the

HBX-DROP GRID SET POINT (see previous

screen) before a DROP command is sent. It can

range from 00.1 hrs to 24.0 hrs in 0.1 hour incre-

ments. These increments are adjusted using the

<INC> and <DEC> soft keys. Press the <DOWN>

soft key to proceed.

With this screen, HBX Mode can be enabled or

disabled. Pressing <CHANGE> allows you to

change the current mode in the next screen.

AC Input Control

ADV/MATE/HBX---------------------

ac input USE

control
DOWN UP CHANGE

NOTE: Before enabling HBX Mode, make sure the

FX is in DROP mode by pressing the <DROP>

soft key. The screen will indicate DROP mode,

allowing the MATE to reset the HBX values.

ADV/MATE/HBX---------------------

ac input USE

control
DROP USE HBX DONE