Voltage start – Outback Power Systems MATE2 User Manual

Page 77

Advertising
background image



ADV/MATE/AGS------------------------

Choose category:

QUIET VOLT

SETUP TIME START PG2

ADV/MATE/AGS/VSTART-----------

volt start 24.4 vdc

24 hr setting
DOWN AGS INC DEC

ADV/MATE/AGS/VSTART------------

volt start 23.6 vdc

2 hr setting

DOWN UP INC DEC

There are three voltage start set points in AGS Mode that the user can adjust. After a generator

is started due to a Voltage Start setting, it will be stopped when the FX completes the absorb

charge or based on the VDC Genstop setting in the AGS Setup menu previously explained.

Voltage Start

NOTE: If the DC Genset is set to YES, the generator will only stop after the battery voltage has

reached the VDC Genstop voltage for 15 minutes.

24-Hour Voltage Set Point

2-Hour Voltage Set Point

To get to the Voltage Start screen, press the

<VOLT START> soft key on the ADV/MATE/

AGS screen.

If the battery voltage falls below this set point, a 24

hour timer starts counting down. Upon reaching

zero, a start command is sent to the generator

unless it is currently Quiet Time. To change the

default settings, use the <INC> and <DEC> soft

keys. When finished, press the <DOWN> soft key

to go to the volt start 2 hr setting screen.

If the battery voltage falls below this set point, a 2

hour timer starts to count down. After reaching

zero, a start command is sent to the generator

unless it is currently Quiet Time. To change the

default settings, use the <INC> and <DEC> soft

keys. When finished, press the <DOWN> soft key

to go to the volt start 2 min setting screen.