Outback Power Systems MATE2 User Manual

Page 87

Advertising
background image



ADV/MATE/AGS/TIMERS ---------

lsstart timer 0 min

DOWN UP

ADV/MATE/AGS/TIMERS---------

lsstop timer 0 min

DOWN UP

ADV/MATE/AGS/TIMERS---------

vdcstop timer 0 min

DOWN UP

ADV/MATE/AGS/TIMERS---------
exstop timer 0 min

DOWN UP

ADV/MATE/AGS/TIMERS ----------

end of TIMERS

menu

UP TOP AGS

This screen displays the load start delay timer

which is adjustable up to 240 minutes, counting

down. The user determines how many minutes

the AC loads must remain above the load start

kw set point before starting the generator. Press

the <DOWN> soft key to view the next TIMERS

screen.

The lsstop timer screen counts down the time the

AC load must remain below the load stop kw be-

fore the generator stops. Press the <DOWN> soft

key to view the vdcstop timer screen.

The vdcstop timer counts down the amount of

time a DC generator is allowed to run. Press

the <DOWN> soft key to view the last TIMERS

screen.

The exstop timer screen displays the amount of

time the generator runs during an exercise period

(1-240 minutes). Press the <DOWN> soft key to

open the end of TIMERS screen.

This is the final TIMERS screen. Press the <AGS>

soft key to view the final AGS screen.