0

DC Genset

In this screen, YES means a DC generator is

present and the AGS routine, which normally

stops the generator upon the FX going to Float or

Silent, will instead stop the generator when the

vdc genstop setting is reached.

This voltage setting will terminate a Voltage Start

command when the battery voltage remains above

it for 15 minutes regardless of the DC Genset

setting. The setting can be adjusted using the

<INC> and <DEC> soft keys. Press the <DOWN>

soft key to view the AGS fault time screen.

AGS Fault Time is the period the generator is

given to connect to the FX system after the AUX

output has been activated. If the generator fails

to connect and provide AC current, the MATE

displays an AGS error. The user can set this time

anywhere from 5-30 minutes by pressing the

<INC> and <DEC> soft keys. Press the <DOWN>

soft key to reach the cool down time screen.

ADV/MATE/AGS/SETUP
dc genset NO

DOWN UP NO YES

NOTE: If you have a generator that produces AC

voltage, maintain the NO status shown on this

screen.

ADV/MATE/AGS/SETUP-----

AGS fault time 17

minutes

DOWN UP INC DEC

VDC Genstop

ADV/MATE/AGS/SETUP-----

vdc genstop: 38.0 vdc

DOWN UP INC DEC

NOTE: The vdc genstop will turn off a generator

even if the dc genset on the previous screen says

<NO>.

Press the <DOWN> soft key to go to the vdc

genstop screen.