Ags quiet time menu • ags volt start menu, Ags volt start menu – Outback Power Systems MATE2 User Manual

Page 98

Advertising
background image



ADV/MATE/AGS/QT----------------

weekday 12:00A

quiet time start
DOWN AGS CHANGE

ADV/MATE/AGS/QT------------------

weekend 12:00A

quiet time start
DOWN UP CHANGE

ADV/MATE/AGS/QT----------------

weekday 12:00A

quiet time stop

DOWN UP CHANGE

ADV/MATE/AGS/QT------------------

weekend 12:00A

quiet time stop

DOWN UP CHANGE

• AGS QUIET TIME Menu

• AGS VOLT START Menu

ADV/MATE/AGS/VSTART----------

volt start 12.2 vdc

24 hr setting
DOWN AGS INC DEC

ADV/MATE/AGS/VSTART------------

volt start 11.0 vdc

2 min setting
DOWN AGS INC DEC

ADV/MATE/AGS/VSTART-----------

volt start 11.8 vdc

2 hr setting

DOWN AGS INC DEC

Volt start 24 hr setting:

24 VDC system = 24.4 vdc

32 VDC system = 32.6 vdc

36 VDC system = 36.6 vdc

48 VDS system = 48.8 vdc

Volt start 2 hr setting:

24 VDC system = 23.6 vdc

32 VDC system = 31.5 vdc

36 VDC system = 35.4 vdc

48 VDS system = 47.2 vdc

Volt start 2 min setting:

24 VDC system = 22.0 vdc

32 VDC system = 29.3 vdc

36 VDC system = 33.0 vdc

48 VDS system = 44.0 vdc

• AGS VOLT START Menu

ADV/MATE/AGS/LS-----------------

load start 0 kw

DOWN AGS INC DEC

ADV/MATE/AGS/LS-----------------

load stop 0 kw

DOWN AGS INC DEC

ADV/MATE/AGS/LS-----------------

load start 1 min

delay

DOWN AGS INC DEC

ADV/MATE/AGS/LS-----

load stop 1 min

delay
DOWN AGS INC DEC