Thermal Considerations

119

AT8050

www.kontron.com

6.1.3

Airflow blockers

It is highly recommended to use airflow blockers (ATCA slot) and AMC airflow blocker in the AT8050 (or any
empty AMC slot) to block any slot open to exterior air. Failure to do so would go against forced air principles
applied on ATCA components, reducing system's cooling efficiency. Moreover, airflow blockers offer a higher
impedance to forced air than typical board, who tend to let more air into slots filled with AT8050 or other
ATCA boards.

6.1.4

System Airflow

The airflow impedance (pressure) curve gives multiple information and tips about thermal operational range
of the system carrying the AT8050. Once volumetric airflow capability of your chassis is known, the PQ curve
can help determine the ambient (room) temperature setpoint that should be used for optimal operation. If
you are using various models of ATCA blades into the same chassis, it is possible to find the best thermal fit.
Having the volumetric airflow value for each chassis slot, is it then possible to decide the layout using the
pressure curves.

Table 6-2:Pressure curve AT8050 with AMC Filler

Figure 6-1:Pressure Curve in Imperial

Test Poin

Airflow (CFM)

Pressure drop
(in H2O)

Airflow (m³/h)

Pressure Drop
(Pa)

1

12,04

0,038

20,46

9,57

2

15,03

0,048

25,54

12,02

3

21,02

0,069

34,00

17,28

4

25,00

0,100

42,48

24,91

5

30,01

0,142

50,99

35,26

6

35,02

0,195

59,50

48,61

7

40,02

0,257

68,00

64,07

8

45,06

0,321

76,55

79,95

9

50,01

0,381

84,97

95,00

0,02

0,07

0,12

0,17

0,22

0,27

0,32

0,37

0,42

10,00

15,00

20,00

25,00

30,00

35,00

40,00

45,00

50,00

55,00

Airflow (CFM)

Pressure (Inch H2O)