BRICK CORE TEMPERATURE SENSOR INSTALLATION

Step 1 Remove the screws by the brick core temperature sensor holes in the

galvanized front panel.

Step 2 Insert the brick core temperature sensors through the holes in the

galvanized front panel. Be sure the sensor marked "upper" is installed

in the upper opening , the sensor marked "lower" is installed in the

lower opening, and the sensor marked "middle" is installed in the center

position (Figure7). The sensor must pass through the blanket insulation

and into the brick core. Holes have not been predrilled through the

insulation. Use the sensors to aid in making a passageway by rotating

them side-to-side while gently pushing inward.

Step 3 Once the brick core sensors are installed, put the screws back into

position in the galvanized front panel to hold the sensors in position

and to provide the electrical ground.

Step 4 Check the non-insulated element terminations to make sure they do

not come within 1/2" of any surface area on the system.

Step 5 Re-install painted front panel using previously removed screws.

DUCTING

For air delivery, the Comfort Plus Commercial

System is equipped with a variable speed supply

air blower. When interfacing with a heat pump, the

A-Coil MUST be placed on the return air side.
To maintain a room temperature of 85

o

F or less in

the mechanical room, a 24" x 24" opening can be

installed in the area or a 6" x 6" non-closing

register can be cut into the return air duct. Refer

to Placement and Clearance Requirements (Page

3.02-3.03) for more information.

The system is factory configured for a left-to-right

or right-to-left airflow. In either airflow direction,

the holes directly above the air outlet on the right

side of the furnace MUST be contained in the

duct system. (See Figure 8 for reference to these

air holes.)

If a down flow configuration is desired, a down flow kit

must be ordered from the factory (Order Item

#1301578) and the system MUST be raised a minimum

of 10" off the ground. An 18" pedestal is available

(Order Item #1301585).

Step 1 Unbox the supply air blower plenum assembly.
Step 2 Remove and discard metal plate securing

supply air blower to plenum assembly.

Risk of improper operation.

Proper installation of the

brick core temperature

sensor is critical to the

operation of the heating

system. Read and follow

installation instructions

carefully.

CAUTION

Comfort Plus Commercial

Installation

n

3.06

Installation

FIGURE 7

HAZARDOUS VOLTAGE:

Risk of electric shock. Can cause injury or death.

w Do install ducting before energizing the system.

w Do NOT operate the system without ducting in-

stalled to both the air inlet and outlet.

w Proper duct design and air flow are critical to

achieve optimum system performance. A poorly

designed duct system and/or improper air flow can

cause system inefficiencies, air noise, and conden-

sate drain problems. In applications where poor air

flow conditions exist along with high humidity, it

may be necessary to install a secondary conden-

sate drain pan. (Order Item #1301576).

WARNING

SUPPLY AIR PLENUM ATTACHMENT

FIGURE 8

Air

Holes

Plenum Support Bracket

Radiant Heat Shield