CONTROL PANEL

Operation of the Comfort Plus Commercial system is automatic. All operational

function settings are stored in a microprocessor in factory preset locations. If

necessary, the user or installer can adjust these locations settings through the

control panel (Figure 1).

Four-Digit LED Display

The four digit LED displays specific operating information. During an editing

process, the function locations and the values set in these locations are displayed

for viewing and adjusting purposes.

AM and PM Indicator Lights

The AM and PM indicator lights are only utilized if the Steffes Time Clock

Module is being installed. With this module installed, the system displays time on

AM/PM intervals and the corresponding light flashes. The system can be

configured to display military time, in which case, both the AM and PM

lights illuminate.

Mode (Edit) Button

Activates the editing menu for changing the operating information of the

system.

Up and

Down Arrow Buttons

Used to scroll up or down when viewing or changing

operating functions.

Interface Port

FOR SERVICE USE ONLY! Allows technician external access for updating software and troubleshooting.

OPERATING STATUS (DIGITAL DISPLAY)

The Comfort Plus Commercial system is set to display various operating information as described below. Press

and release the up arrow to view this data.

Operating Mode - Indicates the current operating mode of the system.

C = Off-Peak (Charge) Time

P = On-Peak (Control) Time

A = Anticipated Peak Time

Outdoor Temperature -“O” followed by a number indicates current outdoor temperature.

Heat Call Status - Indicates the current heat call status being received from the room thermo-

stat. Refer to pages 3.11 and 3.12 for more information on heat call inputs.

Brick Core Charge Level - “CL” (charge level) followed by a number indicates the current

percentage of heat stored in the brick core. “CL:_” represents zero percent and “CL: F” repre-

sents a full core charge level.
Targeted Brick Core Charge Level - “tL” (target level) followed by a number indicates the

current percentage of brick core charge being targeted by the system. A display of “tL:_” indi-

cates a target level of zero percent and “tL: F” indicates a full core charge target level.

Load Control - Current demand (kW) divided by 10. A value of "d 75" is equal to a current

demand of 750kW.

Operation

n

1.02

Comfort Plus Commercial

M

с

т

Operation

A bar illuminates on the lower portion of

the display's second digit whenever the

heating elements are energized.

CONTROL PANEL

FIGURE 1

M

M

M

P

P

M

M

A

A

CAUTION

Editing operating

information may alter

the performance and

operation of the system.