Error Code Description

05

Outdoor sensor (direct wired) temperature reading is out of normal operating range. The sensor

circuit may be open or shorted, the processor control board may be out of calibration, or there

may be an incorrect value in L035. If using power line carrier control, make sure the values in

L020 and L035 have been set appropriately. Otherwise, verify that the outdoor sensor is con-

nected properly. Compare the sensor reading to the value in L113 to verify proper calibration of

the circuit board. Approximate ohm readings are 5°F = 7,646 ohms; 50°F = 2,024 ohms;

95°F = 646 ohms.

06

Outdoor temperature reading from the transmitting device (PLC system) is out of normal operat-

ing range. Check the outdoor sensor attached to the transmitting device and the transmitter for

proper operation.

07

Main processor control board temperature sensor is out of normal operating range. Verify that

none of the clearances have been violated and inspect the condition of the processor control

board.

08

External duct sensor temperature is out of normal operating range. This can indicate an open

sensor, a short in the wiring, or the relay driver board is out of calibration. Take an ohm reading

across the sensor to ensure proper operation, check the wiring, and verify the value in L053.

Compare the sensor reading to the value in L144 to verify proper calibration of the circuit board.

Approximate ohm readings are 60°F = 1552 ohms; 70°F = 1199 ohms; 80°F = 941 ohms.

Max 190°F, Min 0°

09

Auxiliary analog input is out of normal operating range. Currently not used.

10

Discharge air temperature has exceeded maximum standard operating temperatures.

11

Core C thermocouple temperature is out of normal operating range. An open, shorted, or other-

wise defective thermocouple or a circuit board which is out of calibration can cause this. Read

mV DC across the thermocouple. Compare the thermocouple reading to the value in L136 to

verify proper calibration of the circuit board. Approximate DC mV readings are 200°F = 3.8

mV; 700°F = 15.2 mV; 1200°F = 27.0 mV. Max. 1700°F, min 0°F

12

Core D thermocouple temperature is out of normal operating range. An open, shorted, or other-

wise defective thermocouple or a circuit board which is out of calibration can cause this. Read

mV DC across the thermocouple. Compare the thermocouple reading to the value in L137 to

verify proper calibration of the circuit board. Approximate DC mV readings are 200°F = 3.8

mV; 700°F = 15.2 mV; 1200°F = 27.0 mV. Max. 1700°F, min 0°F

13

Core E thermocouple temperature is out of normal operating range. An open, shorted, or other-

wise defective thermocouple or a circuit board which is out of calibration can cause this. Read

mV DC across the thermocouple. Compare the thermocouple reading to the value in L138 to

verify proper calibration of the circuit board. Approximate DC mV readings are 200°F = 3.8

mV; 700°F = 15.2 mV; 1200°F = 27.0 mV. Max. 1700°F, min 0°F

14-16

Not used in Comfort Plus Commercial systems.

17

Load Control Device (4-20mA) is out of normal range. This can indicate an open sensor, a short

in the wiring, or a relay driver board which is out of calibration. Take a mA reading across the

input to ensure proper operation, check the wiring, and verify the value in L053. Compare the

sensor reading to the value in L142 to verify proper calibration of the circuit board. All heating

elements should be turned off. Max. 25mA, min 2mA

18

Pulse reading is not functional. The pulse input reading is indicating 0 load even though there are

elements, 2 minimum, turned on. All loads should be turned off.

19

There is no communication occurring with the relay driver board. The interface cable may be

defective or the relay driver board may be unresponsive. Verify that the values in L090, L091,

and L092 are correct for the application.