C006 Output Control Configuration - Configures the output controls of the Comfort Plus Commercial

system. To determine the value, check the options desired from the list below. Then, add the numbers

from the “Value” column and enter the sum into this location.

Value

Option Selected

3

All 6100 Series Systems.

8

Enables compressor control if there is a "COOL" call during a peak (control) time.

32

If it is a peak (control) period and the Comfort Plus Commercial receives a cooling call,

the compressor will turn off and on in 20 minute intervals (off 20 minutes, on 20 minutes,

off 20 minutes, etc.).

128

Interfaces Comfort Plus Commercial with a heat pump that has a reversing valve which

is energized for heating.

C007

Charge Factor - This configuration should be set to a value of 30.

C008 through C010 configurations are only applicable if the Comfort Plus Commercial system is

being used in conjunction with a heat pump.

C008

Heat Pump Compressor Outdoor Lock-Out Temperature for Off-Peak or Anticipated Peak

Modes - Indicates the outdoor temperature at which the heat pump’s compressor is locked out and not

allowed to operate during an off-peak or anticipated peak period.

C009

Heat Pump Compressor Outdoor Lock-Out Temperature for On-Peak Mode - Indicates the

outdoor temperature at which the heat pump’s compressor is locked out and not allowed to operate

during an on-peak period.

C010

Minimum Discharge Air Temperature - Sets the minimum discharge air temperature the system

targets during a Stage 1 heat call.

C011

Currently not utilized in the 6100 Comfort Plus Commercial systems.

C012

Currently not utilized in the 6100 Comfort Plus Commercial systems.

C013-C021 Time Clock Module Configuration - These configuration settings are used to configure the peak

control times when utilizing the optional Steffes Time Clock Module. Refer to the installation and