Page 17: Line voltage electrical connections

Advertising
background image

Comfort Plus Commercial

Installation

n

3.08

Installation

AIR CONDITIONER/HEAT PUMP INTERFACE

When interfacing the Comfort Plus system with a heat pump, the

indoor coil MUST be placed on the return side of the Comfort Plus

system in a position that will provide even air flow through the coil. If

using a factory supplied return air plenum, the plenum is configured to

be the housing for the indoor coil. Remove the screws to the plenum’s

access cover and slide the coil into place inside the plenum. If not using

a Steffes supplied return air plenum, the installer will need to make

provisions in the plenum to accommodate the coil and air filter.
When interfacing a Comfort Plus system with an air conditioner, the

indoor coil can be placed on either the supply air or the return air side

of the system.
The condensate drain trap, in a heat pump or air conditioner installation,

should be designed for the vacuum in which the system is operating.

Typically, taller traps are better suited for these types of applications.
Refer to the Room Thermostat Connections Diagrams (Figures 14, 15 and 16) for more information on interfacing

the Comfort Plus with a heat pump or air conditioner.

WARNING

Risk of fire. Any one ducting system

MUST NOT contain more than one

air handling (blower) system. If the

application requires multiple Com-

fort Plus systems or it is necessary to

have multiple air handlers share the

same ductwork, you MUST contact

Steffes Corporation. There are

special installation requirements

that MUST be performed in an

application such as this.

LINE VOLTAGE ELECTRICAL CONNECTIONS

In standard configuration, the system is wired for connection to

240V; however, the element circuits can also be connected to

208V. A 208V connection derates the charging input of the

system by 25%. If a system rated specifically for 208V is

required, contact the factory. The controls circuit in the system

MUST be connected to 240V/208V.

277/480V and 347/600V Comfort Plus Commercial

systems are configured to use single feed only.

208/240V System Connections Only: The 60 amp breakers

located in the electrical compartment feed the core charging (ele-

ment) circuits. The 15 amp breaker feeds the controls and blowers

circuit. All 240V/208V systems are factory configured to be field

connected to multiple line voltage circuits. If a single feed line

voltage circuit is desired, an optional single feed kit is available from

the factory.
277/480V and 347/600V System Connections Only: The fuse

block connection points and neutral connection block, located in the

line voltage side of the electrical compartment, feed the core

charging (heating element) circuits. This also provides power and the terminal block connections for the primary

side of the optional control voltage step-down transformer. Adjacent to these terminals are the connection points

for the transformer secondary. See Figure 12B.
To determine the correct wire size required for each circuit feeding the system, refer to the Specifications (Page

A.01) and the system's identification label located on the lower left side of the system. (Reference Sample Label

Figure 11.)
Step 1 Route all line voltage wires through a knockout and into the electrical panel.
Step 2 Make proper field wiring connections to the Comfort Plus Commercial breakers. Refer to the Line Voltage

Wiring Diagrams (Pages A.03 - A.04) for more information on these connections.

HAZARDOUS VOLTAGE: Risk of electric

shock. Can cause injury or death. Do not

energize the system until installation is

complete. Equipment MUST be installed

by a qualified technician in compliance

with all applicable local, state, and

national codes and regulations.

WARNING

w To ensure proper operation and

safety, all line voltage circuits

must be segregated from low

voltage wiring in the system.

w To reduce electro magnetic fields

associated with electrical circuits

and to avoid induced voltage on

sensors and electronic devices, the

circuit phases MUST be alternated

as shown in Figure 12A.

IMPORTANT