Warning, Help menu, Error codes – Steffes 6140 User Manual

Page 30

Advertising
background image

Appendix

HELP MENU

The Comfort Plus Commercial contains a Help Menu which may be accessed through the control panel. To

access the Help Menu, press and release the M button until the faceplate displays “HELP”. Scroll through the

menu by pressing either the up or the down arrow button.
Display

Reading

Description

Fxxx

Firmware Version Number - Indicates the version of software installed.

O xx

Outdoor Temperature - Indicates current outdoor temperature as recognized by the system.

tL:xx

Target Level - Indicates the percentage of brick core charge level the system is targeting. During

peak periods the value displays as "tL_".

CL:xx

Charge Level - Indicates the percentage of heat storage currently in the brick core.

HE x

Heating Elements Active - Indicates the total number of heating elements currently energized.

PC x

Power Line Carrier Channel - Indicates the channel on which the system is set to receive PLC

communication signal.

P x

Power Line Carrier Net Hit Rate Percentage - Indicates the percentage of "GOOD" communication

packets received by the system from the PLC transmitter system.

PS x

Indicates which Specialty Timer the system is currently using. The value displayed will be zero if the

Specialty Timer is not being utilized.

CC_x

Charge Mode Operation - Indicates the charge control method being utilized during off-peak periods.

CA_x

A-Peak Mode Operation - Indicates the charge control method being utilized during anticipated peak

periods.

C1_x

Specialty Timer #1 Charge Mode - Specialty Applications Only.

C2_x

Specialty Timer #2 Charge Mode - Specialty Applications Only.

HUxx

Heat Usage - Indicates the amount of input being dissipated by the system.

A_xx

Target Discharge Air Temperature - Indicates the discharge air temperature that the system is

targeting.

cxxx

Compressor Output Relay Delay Timer - Indicates time remaining before heat pump compressor is
energized. "c ON" indicates the heat pump is energized.

ERROR CODES

The system has an on-board diagnostic system to monitor various operating

conditions. If operating conditions move outside the normal operating range,

an error code is displayed on the faceplate. If there are multiple errors

simultaneously, only the highest priority error code appears. Once corrected,

the next highest priority code will be displayed on the faceplate as “Er—”

(i.e., Er05).

Error Code

Description

04

Discharge air sensor temperature is out of normal operat-

ing range. This can indicate an open sensor, a short in the

wiring, or a circuit board which is out of calibration. Take

an ohm reading across the sensor to ensure proper opera-

tion, check the wiring, and verify the value in L035. Verify

that the supply air blower is connected to the supply blower wiring harness located in the base

of the system. Compare the sensor reading to the value in L112 to verify proper calibration of

the circuit board. Approximate ohm readings are 70°F = 1,199 ohms; 80°F = 941 ohms;

95°F = 646 ohms.

HAZARDOUS VOLTAGE:

Risk of electric shock. Can

cause injury or death.

System may be connected

to more than one branch

circuit. Disconnect power to

all circuits before servicing.

Equipment must be serviced

by a qualified technician.

WARNING

Appendix

n

A.06

Comfort Plus Commercial