Warning, Important, Line voltage electrical connections – Steffes 7140 User Manual

Page 17: Installation

Advertising
background image

Installation

Comfort Plus Commercial Hydronic

Installation

n

3.06

SAMPLE SYSTEM IDENTIFICATION LABEL

FIGURE 8

208/240 SINGLE PHASE

CIRCUIT PHASING CONNECTIONS

FIGURE 9A

LINE VOLTAGE ELECTRICAL CONNECTIONS

In standard configuration, the system is wired for connection to

240V; however, the element circuits can also be connected to

208V. A 208V connection derates the charging input of the

system by 25%. If a system rated specifically for 208V is

required, contact the factory. The controls circuit in the system

MUST be connected to 240V/208V.

277/480V and 347/600V Comfort Plus Commercial

systems are configured to use single feed only.

208/240V System Connections Only: The 60 amp breakers located

in the electrical compartment feed the core charging (element) cir-

cuits. The 15 amp breaker feeds the controls and blowers circuit. All

240V/208V systems are factory configured to be field connected to

multiple line voltage circuits. If a single feed line voltage circuit is

desired, an optional single feed kit is available from the factory.
277/480V and 347/600V System Connections Only: The fuse

block connection points and neutral connection block, located in the

line voltage side of the electrical compartment, feed the core charging

(heating element) circuits. This also provides power and the terminal

block connections for the primary side of the optional control voltage step-down transformer. Adjacent to these

terminals are the connection points for the transformer secondary. See Figure 9B.
To determine the correct wire size required for each circuit feeding the system, refer to the Specifications (Page

A.01-A.02) and the system's identification label located on the lower left side of the system. (Reference Sample

Label Figure 8.)
Step 1 Route all line voltage wires through a knockout and into the electrical panel.
Step 2 Make proper field wiring connections to the Comfort Plus Commercial system. Refer to the Line Volt-

age Wiring Diagrams (Pages A.04 - A.09) for more information on these connections.

HAZARDOUS VOLTAGE: Risk of electric

shock. Can cause injury or death. Do not

energize the system until installation is

complete. Equipment MUST be installed

by a qualified technician in compliance

with all applicable local, state, and

national codes and regulations.

WARNING

w To ensure proper operation and

safety, all line voltage circuits

must be segregated from low

voltage wiring in the system.

w To reduce electro magnetic fields

associated with electrical circuits

and to avoid induced voltage on

sensors and electronic devices,

the circuit phases MUST be alter-

nated as shown in Figure 9A.

IMPORTANT

The 60 AMP breakers are for internal

component protection only. Sizing of the

field wire and breaker size MUST be in

compliance with all applicable local,

state, and national codes and regulations.

Circuit Breakers

LIN

E

1

BLOWERS/CONTROLS CIRCUIT

LIN

E

2

LIN

E

1

LIN

E

2

LIN

E

1

LIN

E

2

LIN

E

1

LIN

E

1

LIN

E

2

To Serv

ice

(Break

er) Panel

CHARGE CIRCUIT #4

CHARGE CIRCUIT #3

LIN

E

2

CHARGE CIRCUIT #1

CHARGE CIRCUIT #2

277/480V AND

347/600V THREE

PHASE

FIGURE 9B