Warning, Safety precautions, Safety devices – Steffes 7140 User Manual

Page 3

Advertising
background image

SAFETY PRECAUTIONS

1. DO NOT energize this heating system while disas-

sembled or without the ceramic heat storage brick in

place.

2. DO NOT operate this heating system without the factory

provided pressure relief valve in place.

3. DO NOT use or store materials that may produce

explosive or flammable gases near the system.

4. DO NOT violate the placement and clearance require-

ments specified in this manual. (Page 3.02-3.03)

5. DO NOT place anything on top of the system.
6. Disconnect power to all circuits before servicing as this

heating system may be connected to more than one

branch circuit.

7. Use caution when working around the heating system as

inlet and outlet piping can be very hot.

8. Installation of and/or service to this system should be

performed by a qualified technician in compliance with

information contained herein and with national, state, and

local codes and requirements.

9. A repeated message display of “CORE FAIL” indicates

a need for service by a qualified technician.

SAFETY DEVICES

The Comfort Plus Commercial Hydronic incorporates safety devices to ensure normal operating temperatures are

maintained. The chart below describes these safety devices:

Comfort Plus Commercial Hydronic

Safety Information

DEVICE NAME

FUNCTION

LOCATION

ON SYSTEM

Core Charging High

Limit Switches

(Auto Reset)

These limit switches monitor brick core charging and

interrupt power to the heating elements if the normal

operating temperature is exceeded.

This linear limit switch monitors the temperature of the

water in the exchanger and interrupts power to the core

blower if a water temperature of 250

o

F is exceeded. If

this limit switch opens, contact a qualified service techni-

cian.

Heat Exchanger

Limit Switch

(Manual Reset)

In the limit bar panel

on the left side of the

brick storage cavity.

Inside base on left side.

This linear limit switch monitors the temperature of the

water in the exchanger and interrupts power to the core

blower if a water temperature of 225

o

F is exceeded.

Outlet Water

Temperature Limit

Switch (Auto Reset)

Inside base on left side.

Pressure Relief Valve

Factory provided,

field installed to outlet

port of furnace.

If the water pressure exceeds 75 psig, the pressure relief

valve opens. Once water pressure of less than 75 psig is

achieved, the valve closes. (30 psig option available.)

WARNING

Risk of explosion. Can cause injury

or death. Operating the system

without the pressure relief valve

installed can cause an explosion.

Connect the pressure relief valve

in a vertical, upright position with

the supplied fittings. DO NOT

modify this assembly. DO NOT cap,

plug, or otherwise obstruct the

outlet of the pressure relief valve.
Risk of fire. Can cause injury or

death. Violation of the clearance

requirements can cause improper

operation of the equipment. Main-

tain the placement and clearance

requirements specified.
Risk of personal injury. Plumbing

and other surfaces can be hot. Use

caution when working near the

system.