Caution – Steffes 7140 User Manual

Page 26

Advertising
background image

C006

Output Control Configuration - Configures the output controls of the Comfort Plus Commercial

Hydronic system. To determine the value, check the options desired from the list below. Then, add the

numbers from the “Value” column and enter the sum into this location. If not used in conjunction with a

heat pump or air conditioner, the value in this location should be set to two (2).

Value

Option Selected

2

Comfort Plus Commercial Hydronic System (Model 7140 )

8

Enables compressor control if there is a "COOL" call during a peak (control) time.

32

If it is a peak (control) period and the Comfort Plus Commercial Hydronic receives a

cooling call, the compressor will turn off and on in 20 minute intervals (off 20 minutes, on

20 minutes, off 20 minutes, etc.).

128

Interfaces Comfort Plus Commercial Hydronic with a heat pump that has a reversing

valve which is energized for heating.

C007

Charge Factor - This configuration should be set to a value of 30.

C008 through C010 configurations are only applicable if the Comfort Plus Commercial Hy-

dronic system is being used in conjunc

t

ion with a heat pump.

C008

Heat Pump Compressor Outdoor Lock-Out Temperature for Off-Peak or Anticipated Peak

Modes - Indicates the outdoor temperature at which the heat pump’s compressor is locked out and not

allowed to operate during an off-peak or ant

i

cipated peak period.

C009

Heat Pump Compressor Outdoor Lock-Out Temperature for On-Peak Mode - Indicates the

outdoor temperature at which the heat pump’s compressor is locked out and not allowed to operate

during an on-peak period.

C010

Minimum Discharge Air Temperature - Sets the minimum discharge air temperature the system

targets during a Stage 1 heat call.

C011 and C012 configurations must be set

for the hottest temperature zone in the

installation. C011 is the highest tempera-

ture the system will target and C012 is the

lowest temperature the system will target

during a heat call. Outdoor reset is done

using these two temperatures. (See graph.)

C011

Maximum Outlet Water Temperature - The value set indicates the maximum outlet water tempera-

ture to be targeted. The targeted outlet water temperature is affected by the values in C001 and C002.

For example, if the value in C001 = 50; C002 = 10; C011 = 180; C012 = 140, then at an outdoor tem-

perature of 30 degrees, the targeted outlet water temperature would be 160 degrees.

C012

Minimum Outlet Water Temperature - The value set

indicates the minimum outlet water temperature to be targeted.

The targeted outlet water temperature is affected by the values

in C001 and C002. For example, if the value in C001 = 50;

C002 = 10; C011 = 180; C012 = 140, then at an outdoor tem-

perature of 30 degrees, the targeted outlet water temperature

would be 160 degrees.

C013-C021 Time Clock Module Configuration - These configura-

tion settings are used to configure the peak control times

when utilizing the optional Steffes Time Clock Module.

Refer to the installation and configuration instructions

included with the module for more information.

CAUTION

Risk of high temperature

water. Can cause property

damage. Improper water

temperature settings can

result in damage to the floor

covering. Make sure the

maximum and minimum water

temperatures are appropri-

ate for the application.

Installation

Installation

n

3.15

Comfort Plus Commercial Hydronic

Example of Outdoor Reset

120

140

160

180

200

10

30

50

Outdoor Temperature

W

a

ter

T

e

m

p

er

atu

re