HELP MENU

The Comfort Plus Commercial Hydronic system contains a "HELP" menu which may be accessed through the

control panel. To access the "HELP" menu, press and release the M button until the faceplate displays

“HELP”. Scroll through this menu by pressing either the up or the down arrow button.
Display

Reading

Description

Fxxx

Firmware Version Number - Indicates the version of software installed.

O xx

Outdoor Temperature - Indicates current outdoor temperature as recognized by the system.

tL:xx

Target Level - Indicates the percentage of brick core charge level the system is targeting. During

peak periods the value displays as "tL_".

CL:xx

Charge Level - Indicates the percentage of heat storage currently in the brick core.

HE x

Heating Elements Active - Indicates the total number of heating elements currently energized.

PC x

Power Line Carrier Channel - Indicates the channel on which the system is set to receive PLC

communication signal.

P x

Power Line Carrier Net Hit Rate Percentage - Indicates the percentage of "GOOD" communica-

tion packets received by the system from the PLC transmitter system.

PS x

Indicates which Specialty Timer the system is currently using. The value displayed will be zero if

the Specialty Timer is not being utilized.

CC_x

Charge Mode Operation - Indicates the charge control method being utilized during off-peak

periods.

CA_x

A-Peak Mode Operation - Indicates the charge control method being utilized during anticipated

peak periods.

C1_x

Specialty Timer #1 Charge Mode - Specialty Applications Only

C2_x

Specialty Timer #2 Charge Mode - Specialty Applications Only

HUxx

Heat Usage - Indicates the amount of input being dissipated by the system.

A_xx

Target Discharge Air Temperature - Indicates the discharge air temperature that the system is

targeting.

cxxx

Compressor Output Relay Delay Timer - Indicates time remaining before heat pump compressor

is energized. "c ON" indicates the heat pump is energized.

ERROR CODES

The Comfort Plus Commercial Hydronic system has an on-board diagnostic system to monitor various operating

conditions. If operating conditions move outside the normal operating range, an error code is displayed on the

faceplate. If there are multiple errors simultaneously, only the highest priority

error code appears. Once corrected, the next highest priority code will be

displayed. Error codes will be displayed on the faceplate as “Er—” (i.e., Er05).

Error Code

Description

03

Outlet water temperature is out of normal operating range.

This can indicate an open sensor, a short in the wiring, or a

circuit board which is out of calibration.

04

Discharge air temperature is out of normal operating range.

This can indicate an open sensor, a short in the wiring, or a

circuit board which is out of calibration.

05

Outdoor sensor (direct wired) temperature reading is out of

normal operating range. The sensor circuit may be open or

shorted, the processor control board may be out of calibration,

or there may be an incorrect value in L035.

HAZARDOUS VOLTAGE:

Risk of electric shock.

Can cause injury or

death. System may be

connected to more than

one branch circuit.

Disconnect power to all

circuits before servic-

ing. Equipment must be

serviced by a qualified

technician.

WARNING

Appendix

Comfort Plus Commercial Hydronic

Appendix

n

A.16

Advertising