PLUMBING

The Comfort Plus Commercial Hydronic heating system MUST be plumbed with a primary loop and

secondary (zone) loops. The primary loop needs to consist of a minimum of 10' of 1" pipe and requires its own

pump* (circulator). The secondary (zone) loops require additional pump(s) to operate effectively. Refer to Typical

Primary Loop (Figure 16) and the Typical System Plumbing Diagrams (Figures 17 and 18) for installation information.

The primary loop serves to regulate heat transfer from the system’s heat exchanger, therefore, the primary loop must

be powered by Comfort Plus Commercial Hydronic control system.

Step 1 Remove the exchanger access panel and locate the pressure relief valve assembly.
Step 2 Connect the pressure relief valve to the outlet

water port on the left side of the Comfort Plus

Commercial Hydronic. It is extremely important

that the following conditions for installation of this

part are met:

· Ensure all connections, including the valve

inlet are clean and free from any foreign

material.

· Use pipe compound sparingly, or tape on

external threads only.

· Mount the pressure relief valve in a vertical,

upright, position directly to the outlet water

port of the system. Under no circumstances

should there be a flow restriction or valve of

any type between the safety relief valve and

the pressure vessel.

Step 3 Use schedule 40 pipe to install a discharge line for the pressure relief valve. This discharge line MUST:

· be connected from the valve outlet with no intervening valve and directed downward to a safe

point of discharge.

· allow complete drainage of both the valve and the discharge line.

· be independently supported and securely anchored to avoid applied stress on the valve.

· be as short and straight as possible.

· terminate freely to atmosphere where any discharge is clearly visible and is at no risk of freezing.

· terminate with a plain end that is not threaded.

· be constructed of a material suitable for exposure to temperatures of 375

o

F or greater.

· be, over its entire length, of a pipe size equal to or greater than that of the valve outlet.

PRESSURE RELIEF VALVE INSTALLATION

Risk of discharged hot water and/or

steam. Can cause personal injury or

property damage. During operation,

the pressure relief valve may dis-

charge large amounts of steam and/or

hot water. To reduce the potential for

bodily injury or property damage,

install a discharge line.

CAUTION

Installation

Installation

n

3.11

Comfort Plus Commercial Hydronic

WARNING

Risk of explosion. Can cause injury or death. The factory supplied

pressure relief valve MUST be connected to the system with the

supplied fittings.

w DO NOT modify this assembly.

w DO NOT cap, plug, or otherwise obstruct the outlet of the

pressure relief valve.

w DO mount the pressure relief valve in a vertical, upright

position.

w This pressure relief valve is sized to service the needs of the Comfort Plus Commercial

Hydronic heating system. If multiple heating systems are being used, pressure relief

valving for the other system MUST be provided separately.

Pressure

Relief Valve

Minimum

BTU Rating

Maximum

Operating Pressure

30 PSI

400,000

20 PSI

75 PSI

500,000

60 PSI