AUXILIARY LOAD CONTROL

The Comfort Plus Commercial Hydronic system can be used to provide control signals to other loads in the

application. To do so, connect low voltage control wires to the "COM" and "NC" or the "COM" and "NO" posi-

tions of the six (6) position low voltage terminal block in the electrical compartment of the Comfort Plus Commer-

cial Hydronic. (See Figure 19.) These contacts are rated for 30 volts, 3 amps maximum.

IMPORTANT

Maximum external load should

not exceed 60 VA on the system's

class II transformer.

TYPICAL SYSTEM PLUMBING

(SHOWN WITH STEFFES AIR HANDLER)

FIGURE 18

It is the responsibility of the installer to prevent involuntary flow of water to the air handler. Not

doing so may cause limit tripping and/or decrease heat pump efficiency. Use of a check valve,

zone valve, or other device may help prevent involuntary flow.

IMPORTANT

Installation

Installation

n

3.13

Comfort Plus Commercial Hydronic

NOTE: During off-peak (charge) periods, the contact is

closed between "COM" and "NC".

TYPICAL AUXILIARY LOAD CONTROL

FIGURE 19

RP

Y

C

R

O

G

Y2

OS

H

W

O2

SC

DS

Auxiliary Control Relay

RELAY

Peak Control

Internal

Output Relay

COM

AP

P

NO

NC

White

Orange

White

Black

Secondary Loop

Primary Loop

Primary

Loop Pump

High Temp

Water

5100 Air

Handler

To

Other
Zones

Mixing

Valve

This Valve Must
Be Open During

Normal Operation

From

Other
Zones

Comfort +

Hydronic

Exchanger

Red

White

-

-

+

Low Temp Radiant Zones

CHECK

VALVE