111 − INSTALLATION

Rev B Mar 2013

2-9

2.4.4 Verifying Pre-wired Connections

6. Check to ensure that all pre-wired cable harness connectors and wire leads between the Control Box

and the following ECS components are secure:

• Recirculation Pump
• Over-Temperature Solenoid
• Outlet Dual Temperature Sensor
• Mixed Temperature Sensor

7. If the ECS was ordered with the MODBUS Communication Option, proceed to step 8. Otherwise, the

ECS installation is complete.

2.4.5 Wiring the Temperature Controller to the MODBUS Control System

Step 8, below, applies to the Eurotherm, Mode 2408 Temperature Controller equipped with a MODBUS
communication board and connected to an Energy Management System (EMS), Building Automation
System (BAS) or computer. The type of communication port (RS232-9, RS232-25, or RS485) mounted on
the EMS, BAS or computer determines the relevant signal leads (Ground, Receive and Transmit) in the
control cable that you connect to the MODBUS device and the Temperature Controller, as described in
Table 2-1.

NOTE

If required, the procedure for adding a communication board to the Temperature
Controller is provided in Appendix A

Table 2-1. MODBUS Communication Signal Connections

2408 TEMP. CONTROLLER

COMPUTER CONTROL CABLE

RS232 9-PIN

RS232 25-PIN

RS485

SIGNAL NAME

TERMINAL

SIGNAL NAME

PIN NO.

PIN NO.

PIN NO.

GROUND

HD

GROUND

5

7

GROUND

RECEIVE

HE

TRANSMIT

3

2

A(-)

TRANSMIT

HF

RECEIVE

2

3

B(+)

8. Refer to Table 2-1, Figure 2-8 and/or the ECS wiring diagram in Appendix B to wire the Ground (HD),

Receive (HE) and Transmit (HF) terminals of the Temperature Controller to the RS232-9, RS232-25
or RS485 connector on the EMS, BAS or computer.

Examples of cable types suitable for this purpose are: Belden 9841, 8761, 3105A, or equivalent.
Ensure that the RS232 or RS485 cable connections do not exceed the following lengths:

• RS232 Cable:

50 feet, maximum

• RS485 Cable:

4,000 feet, maximum

NOTE

For best results, DO NOT run MODBUS communication wiring in the same conduit as
power wiring which can couple excessive noise and/or hum into the MODBUS lines.