1 shell and heads, 2 double-wall u-tube bundle and tubesheets, 3 recirculation pipe and pump – AERCO SWDW68 U-Tube Double-Wall Heaters w/ECS User Manual

Page 23: 4 cxt-e control valve, Ee 3.2.3.2), Figure 3-3), P (3.2.3.3), E (3.2.3.4), He– 111 − functional description

Advertising
background image

HE–

111 − FUNCTIONAL DESCRIPTION

Rev B Mar 2013

3-3

COMPOUND PRESSURE

GAUGE

STEAM INPUT

SOLENOID VALVE

CONDENSATE OUT

PLUGGED DRAIN

TEMPERATURE CONTROLLER

CXT-E CONTROL VALVE

VACUUM BREAKER

PRESSURE AND

TEMPERATURE

RELIEF VALVE

CXT-E ACTUATOR

CONTROL BOX

SHELL

COLD

WATER

INPUT

HOT WATER OUTPUT

LEAK

DETECTION

PORT

RECIRCULATION

PUMP

RECIRCULATION

PIPING

OUTLET MANIFOLD

LOWER SHELL

FLANGE

UPPER SHELL

FLANGE

UPPER HEAD

ASSEMBLY

LOWER HEAD

ASSEMBLY

Figure 3-3. AERCO Double-Wall Heat Exchanger, Model DW-24

3.2.3.1 Shell and Heads

The heat exchanger body incorporates a stainless steel shell, bronze upper head and navy brass
tubesheets, forming a pressure vessel that conforms to ASME standards. The heat exchanger body
encloses the tube bundle and tubesheets.

3.2.3.2 Double-Wall U-Tube Bundle and Tubesheets

The double-wall U-bend copper tubes that conduct steam through the heater shell conform to BOCA
(National Plumbing Code), IAPMO (Uniform Plumbing Code) and NAPHCC (National Standard Plumbing
Code), the three national standards that address double-wall construction. The outer wall of each double-
wall tube is brazed to the upper tubesheet, and the inner wall is brazed to the navy brass lower
tubesheet. Any tube leakage from the air spaces between the inner and outer walls of the double-wall
tubes accumulates in the space between the bottom shell flanges which make up the bottom head. The
accumulated leakage water is discharged through the leak detection port.

3.2.3.3 Recirculation Pipe and Pump

Referring to Figure 3-3, the recirculation pipe and constant-rate recirculation pump deliver a continuous
sample of the heated output water to a 1½-inch pipe junction with the Cold Water Input pipe to regulate
steam flow at the Steam Input (see 3.3.2).

3.2.3.4 CXT-E Control Valve

The CXT-E Control Valve regulates the flow rate of steam into the heat exchanger in response to
positioning control signaling from the Temperature Controller (see 3.3.2). The CXT-E Control Valve
consists of a valve body and linkage to the CXT-E Actuator. The CXT-E Actuator is discussed in 3.3.4.5.