He- 111 − troubleshooting – AERCO SWDW68 U-Tube Double-Wall Heaters w/ECS User Manual

Page 53

Advertising
background image

HE-

111 − TROUBLESHOOTING

Rev B Mar 2013

7-11

Table 7-3. TROUBLESHOOTING – ELECTRONIC CONTROL SYSTEM, continued

NO.

FAULT INDICATION

PROBABLE CAUSE

CORRECTIVE ACTION

T20 Outlet water temperature is

far below setpoint

1. Incorrect Temperature

Controller setting

2. Defective Temperature

Controller.

3. Linkage not properly

connected.

4. Defective Actuator.

5. Control Valve shaft may be

binding

1. Refer to Chapter 4 and check the current setting of the Over-

temperature Switch. Readjust as necessary.

2. Disconnect the cable plug from the Valve Actuator and verify that the

Temperature Controller is generating a control signal greater than
4 mA. If not, replace the Temperature. Controller.

3. Check the Control Valve linkage to verify that it is properly connected

and that the pin in the linkage is in the correct position for the
selected Valve size.

4. Replace the Valve Actuator.

5. Refer to Table 7-2, Fault T12, Corrective Action 2c and perform the

indicated action.

T21 Wide fluctuations occur in Hot

Water Output water
temperature during large flow
changes.

1. Heat exchanger recirculation

pump is not operating.

2. Over-temperature Switch

setting is too low.

3. Over-temperature Solenoid

Valve is leaking or open.

1. Check the power to the recirculation pump.

2.

Refer to Chapter 4 and check the current setting of the Over-
temperature Switch. Readjust as necessary.

3. Inspect the solenoid valve for evidence of leaks. If leaks are

detected, replace the solenoid valve.

T22 Wide fluctuations occur in Hot

Water Output water
temperature under low flow
conditions.

1. DHW Outlet Temperature

Sensor connected to the
Temperature Controller is
intermittent.

2. Mixed water temperature

sensor is open, shorted or
gives inconsistent readings.

3. Recirculation pump has failed

1. Replace DHW Outlet Temperature Sensor at the heat exchanger Hot

Water Output port.

2. Replace mixed water temperature sensor.

3. Replace recirculation pump.

T23

Hot Water Output
temperature above over-
temperature limit, but
solenoid (Dump) valve does
not open.

1. Disconnected or defective

solenoid

2. Defective Over-temperature

Switch

3. Solenoid valve wiring is loose

or reversed.

1. Verify that 24 VDC is present at the solenoid plug between leads

103(+) and 104 (-).

If voltage is present and the solenoid is connected, replace the
solenoid. If 24 VDC is not present, proceed to Item 2, below.

2. Replace Over-Temperature Switch.

3. Verify that solenoid valve wiring is secure and connected per

Figure B-1.