111 − OPERATION

Rev B Mar 2013

5-2

TEMP CONTROLLER

HOLD

RUN

AUTO

MAN

2408

PT.NO.

OVER TEMP SWITCH

PANEL
DOOR

OVER-TEMP
SWITCH

TEMPERATURE

CONTROLLER

POWER
SWITCH

[

WATER TEMPERATURE AT

HOT WATER OUTLET

SETPOINT TEMPERATURE

Figure 5-1. Control Box

9. Referring to Figure 5-2, press the AUTO/MAN pushbutton to toggle the AUTO/MAN display to the

MAN (Manual) mode. The MAN indicator will light.

AUTO

RUN

MAN

HOLD

OP 1

OP 2

SP2

REM

2408

UPPER DISPLAY

LOWER DISPLAY

AUTO/MAN MODE
INDICATORS

AUTO/MAN
PUSHBUTTON

OP1 INDICATOR

ARROW
BUTTONS

Figure 5-2. Temperature Controller

10. The upper display will continue to show the current heat exchanger outlet water temperature, and the

lower display will show the position of the CXT-E Control Valve Actuator in %. When the Manual
mode is initially selected, the lower display will show 0%, indicating that the Control Valve is fully
closed.

11. Using the

▲ arrow button, set the CXT-E Control Valve to the 10% position and monitor the heat

exchanger Hot Water Output water temperature.

12. Continue to open the valve further in 5% increments until the Hot Water Output temperature begins to

increase at a moderate rate.

13. When the Hot Water Output water temperature has increased to within 20°F of the desired setpoint,

press the AUTO/MAN button to set the Temperature Controller to the AUTO mode. The AUTO
indicator will light and the MAN indicator will go off. When the Temperature Controller is in the AUTO

Advertising