AC-105 INSTRUCTIONS - ECS & CXT-E

4-2

Rev B Mar 2013

Automatically adjust the Actuator as follows:

1. Referring to Figure 4-2, loosen the set screw on the Actuator cover.

2. Remove the Actuator cover to access the PC board containing the terminal connections,

DIP switches, Auto-Stroke (Reset) Button and LED.

3. Referring to Figure 4-1, use the power switch to turn on the Control Box and apply 24 VDC power to

the Actuator. (On the terminal strip: pin 2 = +24 VDC, pin 1 = Common).

The LED will light indicating that power is applied to the Control Box.

4. Wait approximately 10 seconds for the unit to perform its self-test. The LED will blink from one to four

times, depending on the size of the Valve, as follows:

Blinks

Valve Size

1

1”

2

1.25” and 2.5”

3

1.5” and 3”

4

2” and 4”

5. For full-stroke automatic adjustment, press the Reset button. The LED will light and the Actuator will

rotate in both directions to find its open and closed Valve position stops.

6. When the automatic adjustment is complete, the LED will blink from one to four times, depending on

the size of the valves, as described in step 4, above.

7. Turn the Control Box power off to disconnect power to the Actuator.

8. Replace the Actuator cover and tighten the set screw.

0

90

neptronic

1 2 3

1

2

3

4

5

1

2

3

DIP SWITCHES (3)

(ALL IN UP POSITION)

AUTO-STROKE

(RESET) BUTTON

LED

TERMINALS

PC BOARD

COVER
SET SCREW

ACTUATOR

Figure 4-2. Actuator Adjustment