A.3.3 clearing the hardware error display, He- 111 − appendix a – AERCO SWDW68 U-Tube Double-Wall Heaters w/ECS User Manual

Page 95

Advertising
background image

HE-

111 − APPENDIX A

Rev B Mar 2013

A-9

Table A-3. Diagnostic Alarms - continued

DISPLAY

MEANING

WHAT TO DO

Err2

Error 2: RAM self-test fail

Return Controller for repair

Err3

Error 3: Watchdog fail

Return Controller for repair.

Err4

Error 4: Keyboard failure. Stuck
button or button was pressed
during power-up

Switch power off and then on, without touching any of the
controller buttons

Err5

Error 5: Faulty internal
communication

Check printed circuit board interconnections. If the fault
cannot be cleared, return the controller for repair.

Err6

Digital filter chip faulty or loose
board inside controller

Return Controller for repair

Err7

PV ID failure

Return Controller for repair

Err8

Module 1 ID failure

Faulty or loose module, or isolation problem

Err9

Module 2 ID failure

Faulty or loose module, or isolation problem

ErrA

Module 3 ID failure

Faulty or loose module, or isolation problem

dCF

DC output failure

Return Controller for repair.

O P E n

Secondary Input Missing or
Disconnected

This error may result from no power to the flow meter (check for
green power light on rear of meter or 0-5V flowmeter signal
connections), or a disconnection of the Molex connector between
feedforward sensor and the Eurotherm controller.

A.3.3 Clearing the Hardware Error Display

To clear a hardware error (HW.ER) and reset the Temperature Controller, proceed as follows:

1. Simultaneously press the Page (

) and Scroll (

) buttons on the Temperature Controller.

2. Using the Up

(▲) arrow button, change the password to “8”.

3. Simultaneously press the Page (

) and Scroll (

) buttons again and observe the Temperature

Controller display. The top line will display “8” and the bottom line will display “NO”.

4. Press the Up

(▲) arrow button to toggle the display from “NO” to “YES”.

5. Simultaneously press the Page (

) and Scroll (

) buttons to “Reset” the Temperature

Controller and clear the hardware error.