4 actuator replacement, He- 111 − corrective maintenance – AERCO SWDW68 U-Tube Double-Wall Heaters w/ECS User Manual

Page 67

Advertising
background image

HE-

111 − CORRECTIVE MAINTENANCE

Rev B Mar 2013

8-13

SHAFT PIN

LOCATION

LINKAGE ADAPTER

INDICATOR
PLATE

0

1

LINKAGE
ASSEMBLY

SCALE

PACKING NUT

VALVE TOP

LINKAGE

GASKET

HEX NUTS (2)

VALVE SHAFT

VALVE BODY

5

CAP SCREW

8-32 HEX NUT
(FAR SIDE)

4

INDICATOR PLATE

(CURVED END)

3

2

1

ITEM

QTY

PART DESCRIPTION

PART NUMBER

1

1

LINKAGE ASSEMBLY

24038-1 (1” TO 3” VALVES)
24038-2 (4” Valve)

2

1

SCALE

59028-1 (1” VALVE)

59028-1.25 (1.25” VALVE)

59028-1.5 (1.5” VALVE)

59028-2 (2” VALVE)

59028-2.5 (2.5” VALVE)

59028-3 ( 3” VALVE)

59028-4 (4” VALVE)

3

2

HEX NUT, 8-32

123322

4

2

CAP SCREW, 3/8-16 x 5/8 LONG

54014

5

1

LINKAGE GASKET

81046

Figure 8-4. linkage Assembly Installation Details

8.2.4 Actuator Replacement

The Actuator includes no repairable parts. Therefore, if the troubleshooting procedures point to the
Actuator as the cause of the fault, replace it as described in the following steps:

46. Disconnect and lock-out/tag-out the AC power supplied to the Control Box. Use a voltmeter to ensure

that all voltages are zero before continuing.

47. Disconnect the Control Box cable connected to the Actuator.

48. Use an 8-mm wrench to loosen the hex nuts securing the Actuator to the linkage shaft.

49. Completely remove the defective Actuator from the shaft.

50. To install a replacement Actuator, depress and hold the clutch button (see Figure 8-5) and rotate the

pointer to approximately 80° on the dial. Release the clutch.

Advertising