1 valve shaft seal retainer replacement, He- 111 − corrective maintenance – AERCO SWDW68 U-Tube Double-Wall Heaters w/ECS User Manual

Page 61

Advertising
background image

HE-

111 − CORRECTIVE MAINTENANCE

Rev B Mar 2013

8-7

Table 8-2. PARTS LIST FOR VALVE ASSEMBLIES, TYPE CXT-E ( SIZES 2.50” TO 4.00”),

continued

VALVE SIZE AND PART NUMBERS

ITEM

QTY

PART NAME

2.50 INCH

3.00 INCH

4.00 INCH

26

1

LINKAGE

24038-1

24038-1

24038-2

27

1

ACTUATOR

69009

69009

69009

28

1

SCALE

59028-
2.50

59028-3

59028-4

29

1

GASKET

81046

81046

81046

30

2

HEX NUT, 8-32

123332

123322

123322

31

1

PILOT SPRING BACKUP
WASHER

N/A

N/A

122246

8.2.1 Valve Shaft Seal Retainer Replacement

WARNING

BEFORE PROCEEDING WITH THIS OPERATION, ENSURE THAT THE CONTROL
VALVE HAS BEEN ISOLATED FROM THE STEAM SUPPLY. LIVE STEAM CAN
CAUSE SERIOUS BURNS TO PERSONNEL.

WARNING

ENSURE THAT ELECTRICAL POWER TO THE ELECTRONIC CONTROL SYSTEM
AND ACTUATOR HAS BEEN DISCONNECTED. SERIOUS INJURY TO PERSONNEL
CAN RESULT IF THIS WARNING IS NOT OBSERVED.

To replace the valve shaft seal retainer proceed as follows:

1. Referring to Figure 8-1 or Figure 8-2, loosen the hex nuts (17) under the indicator plate approximately

one-half turn clockwise.

2. Disconnect the linkage adapter from the valve shaft (16) by turning the shaft clockwise (as viewed

from above). If the valve shaft cannot be turned by hand, use an open-end wrench to turn the
“double-nuts” on the shaft until it disengages the linkage adapter threads.

3. Remove the indicator plate from the Valve shaft (16).

4. Remove the two cap screws (19) securing the linkage assembly (26) to the Valve top (21).

5. With the Actuator assembly (27) still attached, remove the complete linkage assembly (26) from the

valve top. Also, remove the gasket (29).

6. If the packing nut (18) is leaking or binding the Valve shaft, replace it.

7. Measure and record the current position of the hex nuts (17) from the end of the Valve shaft (16).

This will simplify adjustment of the Actuator linkage during reassembly.

8. Completely remove the hex nuts (17) from the Valve shaft (16).

9. Remove the packing nut (18) and the packing assembly (20) from the Valve body.

Advertising