2 adjusting the over-temperature alarm limit, And table 4-1 – AERCO SWDW68 U-Tube Double-Wall Heaters w/ECS User Manual

Page 32

Advertising
background image

AC-105 INSTRUCTIONS - ECS & CXT-E

4-4

Rev B Mar 2013

Table 4-1. Temperature Controller Operating Controls, Indicators and Displays

CONTROL /
INDICATOR

MEANING

FUNCTION

OP1

Output 1 Indicator

OP1 lights when a 4-to-20 mA signal is supplied to the
Actuator, or when the valve position is above 0%.

OP2

Output 2 Indicator

Not used for the ECS application

SP2

Setpoint 2 Indicator

Not used for the ECS application

REM

Remote Setpoint
Indicator

REM lights when the ECS is set up to be controlled by
a Remote (MODBUS) signal.
REM will flash when MODBUS communication is
active.

AUTO

MAN

Auto/Manual Button
and Indicators

Pressing the button toggles the Controller between the
automatic (AUTO) and manual (MAN) modes.
• AUTO lights when in the automatic mode.
• MAN lights when in the manual mode.

When entering the MAN mode, the Valve position is
reset to 0%.

RUN

HOLD

Run/Hold Button
and Indicators


Not used for ECS application

Page Button

Press the Page button to select a new list of
parameters

Scroll Button

Press the Scroll button to select a new parameter in a
list

Down Button

Press the Down button to decrease the value shown in
the lower display

Up Button

Press the UP button to increase the value shown in the
lower display

4.3.2 Adjusting the Over-Temperature Alarm Limit

Adjust the over-temperature alarm limit setting using the controls and displays illustrated in Figure 4-4
and described in Table 4-2. Adjust the over-temperature alarm limit as follows:

OVER-TEMPERATURE ALARM LIMIT ADJUSTMENT

The over-temperature alarm limit setting is adjusted using the controls and display on the Over-
Temperature Switch. The controls and display are illustrated and described in Figure 4-4 and Table 4-2. If
necessary, over-temperature alarm limit adjustment is accomplished as follows:

1. With the Control Box door open, set the ON/OFF POWER switch on the right side to the ON position.

2. Press the SET button on the Over-Temperature Switch. SP will appear in the display.

3. Press the SET button again. The current over-temperature limit value stored in memory will be

displayed (default = 160°F).