0BChapter 1: Product introduction

TruVision Mini PTZ 12X Camera User Manual

3

System requirements

For proper operation, adhere to the following operational, cable, and power
requirements for TruVision PTZ Mini 12X cameras.

Figure 1: Example of a system

1. Monitor A

2. Monitor B

3. Control keypad

4. DVR /Multiplxer/ Quad/ Switcher

5. Dome camera

6. Repeater

Cable requirements

Table 1 below lists the requirements for the cables that connect to the dome camera.

Table 1: Recommended cable requirements

Operation

Cable requirement

Max. length

feet

meters

Data (RS-485) STP (shielded twisted-pair) cable

Cat-5 cable recommended. If the total cable length
exceeds 1219 m (4000 feet), using a repeater to
maintain the signal is recommended.

4000 1219

Video

75 ohm coaxial cable with BNC ends

1600

486

Alarm

Cat-5 cable recommended.

1250

381

Power

24 VAC cable. To determine the size of cable needed for individual applications, see
“Power cable size and length requirements” on page 4.