Toa FS-970 SERIES User Manual

Page 31

Advertising
background image

31

9.4.5. Connecting a single emergency power supply panel to power amplifiers

The figure below shows the method of connecting the Emergency Power Supply Panel DS-029B to the power
amplifier panel. Refer to the figure when expanding power amplifier panels or designing the power amplifier
rack.

• Only a single power amplifier panel (up to 120 W) can be connected per output terminal of the emergency

power supply panel.

• When using the 240 W power amplifier panel, connect it to parallel-connected outputs 1 and 2 (or 3 and 4) of

the emergency power supply panel.

• When using the 360 W power amplifier panel, connect the emergency power supply panel's outputs 1 and 2

(or 3 and 4) separately to individual power amplifier panels.

When using the PA-1230B (120 W)

First PA-1230B unit

Second PA-1230 unit

Third PA-1230B unit

Fourth PA-1230B unit

Power amplifier panel's
rear-mounted terminal block

Emergency power supply
panel's (DS-029B)
rear-mounted terminal block

When using the PA-2440B (240 W)

First PA-2440B unit

Second PA-2440 unit

Power amplifier panel's
rear-mounted terminal block

Emergency power supply
panel's (DS-029B)
rear-mounted terminal block

When using the PA-3640B (360 W)

First PA-3640B unit

Second PA-3640B unit

Power amplifier panel's
rear-mounted terminal block

Emergency power supply
panel's (DS-029B)
rear-mounted terminal block

Advertising