3.2. About the Emergency Power Supply
3.2.1. Selection of the emergency power supply panel and battery
The emergency PA system is designed to operate on both the main power supply and emergency power
supply. Because the emergency system needs to be operated for ten minutes or more during a power failure,
the emergency power supply suited to the system scale is required. The FS-970 series systems require the
emergency power supply panel DS-029B and Ni-Cd battery NDC-2435 or NDC-2460. The following table
provides guidelines on the number of emergency power supply panels and Ni-Cd batteries necessary for the
system.
Expansion power supply
AD-011
AD-031B
None (JP-0410's internal power supply only)
Rated output
No. of connected emergency remote control units
PA-1230B
PA-2440B
PA-3640B
0
1
2
3
4
5
6
7
8
Power amplifier panel
composition
Operation section/control section
Power amplifier panel
Battery composition
Quick reference table for emergency battery composition
No. of zones of the main rack and emergency remote control unit
NDC-2435
NDC-2460
Battery
No. of emergency power supply panels DS-029B
50
30
30
20
10
10
120
90
70
60
50
40
30
30
30
60
40
30
30
20
10
10
10
180
150
120
100
90
70
60
50
50
330
270
220
190
160
140
130
110
100
330
310
260
220
190
170
150
140
120
330
330
330
330
330
310
280
250
230
3.5AH
1
1
a
1
1
a
6AH
120W
1
6AH
1
1
a
3.5AH
3.5AH
2
1
b
6AH
6AH
2
1
b
7AH
6AH
2
1
2
c
12AH
6AH
3
2
c
240W
1
360W
1
Notes
• This table assumes that the main rack system and emergency remote control unit are identical in the
number of broadcast zones. It is also assumed that no other components are connected other than the EP-
029, EP-0510, EP-059R, JP-039, and JP-0410, and that any component is not connected to the emergency
power-off output or emergency output. In some systems, the number of zones may be less than those
shown in the above table.
• Refer to the connection examples on p. 27-30 for connection methods a-d of the Emergency Power Supply
Panel DS-029B.
3.2.2. DC power supply panel expansion
When multiple operation sections or emergency remote control units are connected to the main rack, the DC
power supply panel is required in addition to the Emergency Power Supply Panel DS-029B. For its
connection, refer to "DC Power Supply Panel Connection" on p. 34.
0 unit
70
160
30
Maximum zone Nos. vs. connected remote control unit Nos.
1 unit
50
130
20
2 unit
40
100
10
3 unit
30
80
4 unit
30
70
5 unit
20
60
6 unit
10
50
7 unit
10
50
8 unit
10
40
Note
Depending upon the connection method of the JP-0410's internal power supply/ expansion power supply to
expansion equipment (EP-029, EP-059R, JP-039, etc.), the number of zones may lower those shown in the
above table. When using other combinations not shown in the table, contact the shop from where you
purchased the unit.
Expansion power supply is required.
Connection of emergency power supply panel DS-029B