3.2. About the Emergency Power Supply

3.2.1. Selection of the emergency power supply panel and battery

The emergency PA system is designed to operate on both the main power supply and emergency power
supply. Because the emergency system needs to be operated for ten minutes or more during a power failure,
the emergency power supply suited to the system scale is required. The FS-970 series systems require the
emergency power supply panel DS-029B and Ni-Cd battery NDC-2435 or NDC-2460. The following table
provides guidelines on the number of emergency power supply panels and Ni-Cd batteries necessary for the
system.

Expansion power supply

AD-011

AD-031B

None (JP-0410's internal power supply only)

Rated output

No. of connected emergency remote control units

PA-1230B

PA-2440B

PA-3640B

0

1

2

3

4

5

6

7

8

Power amplifier panel

composition

Operation section/control section

Power amplifier panel

Battery composition

Quick reference table for emergency battery composition

No. of zones of the main rack and emergency remote control unit

NDC-2435

NDC-2460

Battery

No. of emergency power supply panels DS-029B

50

30

30

20

10

10

120

90

70

60

50

40

30

30

30

60

40

30

30

20

10

10

10

180

150

120

100

90

70

60

50

50

330

270

220

190

160

140

130

110

100

330

310

260

220

190

170

150

140

120

330

330

330

330

330

310

280

250

230

3.5AH

1

1

a

1

1

a

6AH

120W

1

6AH

1

1

a

3.5AH

3.5AH

2

1

b

6AH

6AH

2

1

b

7AH

6AH

2

1

2

c

12AH

6AH

3

2

c

240W

1

360W

1

Notes
• This table assumes that the main rack system and emergency remote control unit are identical in the

number of broadcast zones. It is also assumed that no other components are connected other than the EP-
029, EP-0510, EP-059R, JP-039, and JP-0410, and that any component is not connected to the emergency
power-off output or emergency output. In some systems, the number of zones may be less than those
shown in the above table.

• Refer to the connection examples on p. 27-30 for connection methods a-d of the Emergency Power Supply

Panel DS-029B.

3.2.2. DC power supply panel expansion

When multiple operation sections or emergency remote control units are connected to the main rack, the DC
power supply panel is required in addition to the Emergency Power Supply Panel DS-029B. For its
connection, refer to "DC Power Supply Panel Connection" on p. 34.

0 unit

70

160

30

Maximum zone Nos. vs. connected remote control unit Nos.

1 unit

50

130

20

2 unit

40

100

10

3 unit

30

80

4 unit

30

70

5 unit

20

60

6 unit

10

50

7 unit

10

50

8 unit

10

40

Note
Depending upon the connection method of the JP-0410's internal power supply/ expansion power supply to
expansion equipment (EP-029, EP-059R, JP-039, etc.), the number of zones may lower those shown in the
above table. When using other combinations not shown in the table, contact the shop from where you
purchased the unit.

Expansion power supply is required.